6-18
L60 Line Phase Comparison Relay
GE Multilin
6.4 RECORDS
6 ACTUAL VALUES
6
6.4.2 EVENT RECORDS
PATH: ACTUAL VALUES
RECORDS
EVENT RECORDS
The Event Records menu shows the contextual data associated with up to the last 1024 events, listed in chronological
order from most recent to oldest. If all 1024 event records have been filled, the oldest record will be removed as a new
record is added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated
with the event trigger. Refer to the
COMMANDS CLEAR RECORDS
menu for clearing event records.
6.4.3 OSCILLOGRAPHY
PATH: ACTUAL VALUES
RECORDS
OSCILLOGRAPHY
This menu allows the user to view the number of triggers involved and number of oscillography traces available. The
‘cycles per record’ value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillogra-
phy section of Chapter 5 for further details.
A trigger can be forced here at any time by setting "Yes" to the
FORCE TRIGGER?
command. Refer to the
COMMANDS
CLEAR RECORDS
menu for clearing the oscillography records.
6.4.4 DATA LOGGER
PATH: ACTUAL VALUES
RECORDS
DATA LOGGER
The
OLDEST SAMPLE TIME
is the time at which the oldest available samples were taken. It will be static until the log gets full,
at which time it will start counting at the defined sampling rate. The
NEWEST SAMPLE TIME
is the time the most recent sam-
ples were taken. It counts up at the defined sampling rate. If Data Logger channels are defined, then both values are static.
Refer to the
COMMANDS
CLEAR RECORDS
menu for clearing data logger records.
EVENT RECORDS
EVENT: XXXX
RESET OP(PUSHBUTTON)
↓
MESSAGE
EVENT: 3
POWER ON
EVENT 3
DATE: 2000/07/14
MESSAGE
EVENT: 2
POWER OFF
EVENT 3
TIME: 14:53:00.03405
MESSAGE
EVENT: 1
EVENTS CLEARED
Date and Time Stamps
OSCILLOGRAPHY
FORCE TRIGGER?
No
Range: No, Yes
MESSAGE
NUMBER OF TRIGGERS:
0
MESSAGE
AVAILABLE RECORDS:
0
MESSAGE
CYCLES PER RECORD:
0.0
MESSAGE
LAST CLEARED DATE:
2000/07/14
15:40:16
DATA LOGGER
OLDEST SAMPLE TIME:
2000/01/14 13:45:51
MESSAGE
NEWEST SAMPLE TIME:
2000/01/14 15:21:19
Содержание L60
Страница 2: ......
Страница 4: ......
Страница 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Страница 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 78: ...3 36 L60 Line Phase Comparison Relay GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3...
Страница 368: ...8 28 L60 Line Phase Comparison Relay GE Multilin 8 2 SINGLE POLE TRIPPING 8 THEORY OF OPERATION 8...
Страница 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Страница 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Страница 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...