GE Multilin
L60 Line Phase Comparison Relay
5-67
5 SETTINGS
5.4 FLEXLOGIC™
5
5.4.2 FLEXLOGIC™ RULES
When forming a FlexLogic™ equation, the sequence in the linear array of parameters must follow these general rules:
1.
Operands must precede the operator which uses the operands as inputs.
2.
Operators have only one output. The output of an operator must be used to create a virtual output if it is to be used as
an input to two or more operators.
3.
Assigning the output of an operator to a Virtual Output terminates the equation.
4.
A timer operator (e.g. "TIMER 1") or virtual output assignment (e.g. " = Virt Op 1") may only be used once. If this rule is
broken, a syntax error will be declared.
5.4.3 FLEXLOGIC™ EVALUATION
Each equation is evaluated in the order in which the parameters have been entered.
FlexLogic™ provides latches which by definition have a memory action, remaining in the set state after the
set input has been asserted. However, they are
volatile
; i.e. they reset on the re-application of control
power.
When making changes to settings, all FlexLogic™ equations are re-compiled whenever any new setting
value is entered, so all latches are automatically reset. If it is necessary to re-initialize FlexLogic™ during
testing, for example, it is suggested to power the unit down and then back up.
Table 5–9: FLEXLOGIC™ OPERATORS
TYPE
SYNTAX
DESCRIPTION
NOTES
Editor
INSERT
Insert a parameter in an equation list.
DELETE
Delete a parameter from an equation list.
End
END
The first END encountered signifies the last entry in
the list of processed FlexLogic™ parameters.
One Shot
POSITIVE ONE SHOT One shot that responds to a positive going edge.
A ‘one shot’ refers to a single input gate
that generates a pulse in response to an
edge on the input. The output from a ‘one
shot’ is True (positive) for only one pass
through the FlexLogic™ equation. There is
a maximum of 64 ‘one shots’.
NEGATIVE ONE
SHOT
One shot that responds to a negative going edge.
DUAL ONE SHOT
One shot that responds to both the positive and
negative going edges.
Logic
Gate
NOT
Logical Not
Operates on the previous parameter.
OR(2)
↓
OR(16)
2 input OR gate
↓
16 input OR gate
Operates on the 2 previous parameters.
↓
Operates on the 16 previous parameters.
AND(2)
↓
AND(16)
2 input AND gate
↓
16 input AND gate
Operates on the 2 previous parameters.
↓
Operates on the 16 previous parameters.
NOR(2)
↓
NOR(16)
2 input NOR gate
↓
16 input NOR gate
Operates on the 2 previous parameters.
↓
Operates on the 16 previous parameters.
NAND(2)
↓
NAND(16)
2 input NAND gate
↓
16 input NAND gate
Operates on the 2 previous parameters.
↓
Operates on the 16 previous parameters.
XOR(2)
2 input Exclusive OR gate
Operates on the 2 previous parameters.
LATCH (S,R)
Latch (Set, Reset) - reset-dominant
The parameter preceding LATCH(S,R) is
the Reset input. The parameter preceding
the Reset input is the Set input.
Timer
TIMER 1
↓
TIMER 32
Timer set with FlexLogic™ Timer 1 settings.
↓
Timer set with FlexLogic™ Timer 32 settings.
The timer is started by the preceding
parameter. The output of the timer is
TIMER #.
Assign
Virtual
Output
= Virt Op 1
↓
= Virt Op 96
Assigns previous FlexLogic™ parameter to Virtual
Output 1.
↓
Assigns previous FlexLogic™ parameter to Virtual
Output 96.
The virtual output is set by the preceding
parameter
CAUTION
Содержание L60
Страница 2: ......
Страница 4: ......
Страница 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Страница 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 78: ...3 36 L60 Line Phase Comparison Relay GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3...
Страница 368: ...8 28 L60 Line Phase Comparison Relay GE Multilin 8 2 SINGLE POLE TRIPPING 8 THEORY OF OPERATION 8...
Страница 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Страница 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Страница 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...