5-60
L60 Line Phase Comparison Relay
GE Multilin
5.4 FLEXLOGIC™
5 SETTINGS
5
The operands available for this relay are listed alphabetically by types in the following table.
Table 5–7: L60 FLEXLOGIC™ OPERANDS (Sheet 1 of 7)
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
CONTROL
PUSHBUTTONS
CONTROL PUSHBTN n ON
Control Pushbutton
n
(
n
= 1 to 7) is being pressed.
DIRECT INPUT/
OUTPUT
CHANNEL
MONITORING
DIR IO CH1(2) CRC ALARM
DIR IO CRC ALARM
DIR IO CH1(2) UNRET ALM
DIR IO UNRET ALM
The rate of Direct Input messages received on Channel 1(2) and failing the
CRC exceeded the user-specified level.
The rate of Direct Input messages failing the CRC exceeded the user-
specified level on Channel 1 or 2.
The rate of returned direct input/output messages on Channel 1(2) exceeded
the user-specified level (ring configurations only).
The rate of returned direct input/output messages exceeded the user-
specified level on Channel 1 or 2 (ring configurations only).
ELEMENT:
50DD Supervision
50DD SV
Disturbance Detector is supervising
ELEMENT:
87PC Phase
Comparison
87PC PKP
87PC OP
87PC DPO
87PC TRANS BLOCK OP
87PC FDL OP
87PC FDH OP
87PC BKR ECHO PKP
Phase Comparison has picked up
Phase Comparison has operated
Phase Comparison has dropped out
Phase Comparison transient blocking has operated
Fault Detector Low has operated
Fault Detector High has operated
Open Breaker Echo of Phase Comparison has picked up
ELEMENT:
Autoreclose
(1P/3P)
AR ENABLED
AR DISABLED
AR RIP
AR 1-P RIP
AR 3-P/1 RIP
AR 3-P/2 RIP
AR 3-P/3 RIP
AR 3-P/4 RIP
AR LO
AR BKR1 BLK
AR BKR2 BLK
AR CLOSE BKR1
AR CLOSE BKR2
AR FORCE 3-P TRIP
AR SHOT CNT > 0
AR SHOT CNT = 1
AR SHOT CNT = 2
AR SHOT CNT = 3
AR SHOT CNT = 4
AR ZONE 1 EXTENT
AR INCOMPLETE SEQ
AR RESET
Autoreclosure is enabled and ready to perform
Autoreclosure is disabled
Autoreclosure is in "Reclose in Progress" state
A single-pole reclosure is in progress
A three-pole reclosure is in progress, via Dead Time 1
A three-pole reclosure is in progress, via Dead Time 2
A three-pole reclosure is in progress, via Dead Time 3
A three-pole reclosure is in progress, via Dead Time 4
Autoreclosure is in lockout state
Reclosure of Breaker 1 is blocked
Reclosure of Breaker 2 is blocked
Reclose Breaker 1 signal
Reclose Breaker 2 signal
Force any trip to a three-phase trip
The first ‘CLOSE BKR X’ signal has been issued
Shot count is equal to 1
Shot count is equal to 2
Shot count is equal to 3
Shot count is equal to 4
The Zone 1 Distance function must be set to the extended overreach value
The incomplete sequence timer timed out
AR has been reset either manually or by the reset timer
ELEMENT:
Auxiliary
Overvoltage
AUX OV1 PKP
AUX OV1 DPO
AUX OV1 OP
Auxiliary Overvoltage element has picked up
Auxiliary Overvoltage element has dropped out
Auxiliary Overvoltage element has operated
ELEMENT:
Auxiliary
Undervoltage
AUX UV1 PKP
AUX UV1 DPO
AUX UV1 OP
Auxiliary Undervoltage element has picked up
Auxiliary Undervoltage element has dropped out
Auxiliary Undervoltage element has operated
ELEMENT:
Breaker Arcing
BKR ARC 1 OP
BKR ARC 2 OP
Breaker Arcing Current 1 has operated
Breaker Arcing Current 2 has operated
ELEMENT
Breaker Failure
BKR FAIL 1 RETRIPA
BKR FAIL 1 RETRIPB
BKR FAIL 1 RETRIPC
BKR FAIL 1 RETRIP
BKR FAIL 1 T1 OP
BKR FAIL 1 T2 OP
BKR FAIL 1 T3 OP
BKR FAIL 1 TRIP OP
Breaker Failure 1 re-trip phase A (only for 1-pole schemes)
Breaker Failure 1 re-trip phase B (only for 1-pole schemes)
Breaker Failure 1 re-trip phase C (only for 1-pole schemes)
Breaker Failure 1 re-trip 3-phase
Breaker Failure 1 Timer 1 is operated
Breaker Failure 1 Timer 2 is operated
Breaker Failure 1 Timer 3 is operated
Breaker Failure 1 trip is operated
BKR FAIL 2
Same set of operands as shown for BKR FAIL 1
Содержание L60
Страница 2: ......
Страница 4: ......
Страница 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Страница 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 78: ...3 36 L60 Line Phase Comparison Relay GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3...
Страница 368: ...8 28 L60 Line Phase Comparison Relay GE Multilin 8 2 SINGLE POLE TRIPPING 8 THEORY OF OPERATION 8...
Страница 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Страница 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Страница 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...