B-28
L60 Line Phase Comparison Relay
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
6705
Load Encroachment Pickup Delay
0 to 65.535
s
0.001
F001
0
6706
Load Encroachment Reset Delay
0 to 65.535
s
0.001
F001
0
6707
Load Encroachment Block
0 to 65535
---
1
F300
0
6708
Load Encroachment Target
0 to 2
---
1
F109
0 (Self-reset)
6709
Load Encroachment Events
0 to 1
---
1
F102
0 (Disabled)
670A
Reserved (6 items)
0 to 65535
---
1
F001
0
Trip Output (Read/Write Setting)
6800
Trip Mode
0 to 2
---
1
F195
0 (Disabled)
6801
Trip 3-Pole Input1
0 to 65535
---
1
F300
0
6802
Trip 3-Pole Input2
0 to 65535
---
1
F300
0
6803
Trip 3-Pole Input3
0 to 65535
---
1
F300
0
6804
Trip 3-Pole Input4
0 to 65535
---
1
F300
0
6805
Trip 3-Pole Input5
0 to 65535
---
1
F300
0
6806
Trip 3-Pole Input6
0 to 65535
---
1
F300
0
6807
Trip 1-Pole Input1
0 to 65535
---
1
F300
0
6808
Trip 1-Pole Input2
0 to 65535
---
1
F300
0
6809
Trip 1-Pole Input3
0 to 65535
---
1
F300
0
680A
Trip 1-Pole Input4
0 to 65535
---
1
F300
0
680B
Trip 1-Pole Input5
0 to 65535
---
1
F300
0
680C
Trip 1-Pole Input6
0 to 65535
---
1
F300
0
680D
Trip Reclose Input1
0 to 65535
---
1
F300
0
680E
Trip Reclose Input2
0 to 65535
---
1
F300
0
680F
Trip Reclose Input3
0 to 65535
---
1
F300
0
6810
Trip Reclose Input4
0 to 65535
---
1
F300
0
6811
Trip Reclose Input5
0 to 65535
---
1
F300
0
6812
Trip Reclose Input6
0 to 65535
---
1
F300
0
6813
Trip Force 3-Pole
0 to 65535
---
1
F300
0
6814
Trip Pilot Priority
0 to 65.535
s
0.001
F001
0
6815
Breaker Phase A Open
0 to 65535
---
1
F300
0
6816
Breaker Phase B Open
0 to 65535
---
1
F300
0
6817
Breaker Phase C Open
0 to 65535
---
1
F300
0
6818
Trip Events
0 to 1
---
1
F102
0 (Disabled)
6819
Reverse Fault Operand
0 to 65535
---
1
F300
0
681A
Trip Delay On Evolving Faults
0 to 65.535
s
0.001
F001
0
681B
Reserved (5 items)
0 to 1
---
1
F001
0
Open Pole Detect (1P) (Read/Write Setting)
6820
Open Pole Function
0 to 1
---
1
F102
0 (Disabled)
6821
Open Pole Block
0 to 65535
---
1
F300
0
6822
Open Pole Voltage Supervision
0 to 1
---
1
F102
0 (Disabled)
6823
Open Pole Current Pickup
0 to 30
pu
0.001
F001
50
6824
Open Pole Target
0 to 2
---
1
F109
0 (Self-reset)
6825
Open Pole Events
0 to 1
---
1
F102
0 (Disabled)
6826
Open Pole Line XC0
300 to 9999.9
ohms
0.1
F003
99999
6828
Open Pole Line XC1
300 to 9999.9
ohms
0.1
F003
99999
682A
Open Pole Remote Current Pickup
0 to 30
pu
0.001
F001
50
682B
Reserved (5 items)
0 to 1
---
1
F001
0
Autoreclose 1P 3P (Read/Write Setting)
6890
Autoreclose Mode
0 to 3
---
1
F080
0 (1 & 3 Pole)
6891
Autoreclose Maximum Number of Shots
1 to 4
---
1
F001
2
6892
Autoreclose Block Breaker 1
0 to 65535
---
1
F300
0
6893
Autoreclose Close Time Breaker 1
0 to 655.35
s
0.01
F001
10
6894
Autoreclose Breaker Manual Close
0 to 65535
---
1
F300
0
6895
Autoreclose Function
0 to 1
---
1
F102
0 (Disabled)
6896
Autoreclose Block Time Manual Close
0 to 655.35
s
0.01
F001
1000
Table B–9: MODBUS MEMORY MAP (Sheet 21 of 47)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание L60
Страница 2: ......
Страница 4: ......
Страница 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Страница 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 78: ...3 36 L60 Line Phase Comparison Relay GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3...
Страница 368: ...8 28 L60 Line Phase Comparison Relay GE Multilin 8 2 SINGLE POLE TRIPPING 8 THEORY OF OPERATION 8...
Страница 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Страница 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Страница 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...