
GE Multilin
L60 Line Phase Comparison Relay
2-17
2 PRODUCT DESCRIPTION
2.2 SPECIFICATIONS
2
2.2.11 TYPE TESTS
Electrical fast transient: ANSI/IEEE C37.90.1
IEC 61000-4-4
IEC 60255-22-4
Oscillatory transient:
ANSI/IEEE C37.90.1
IEC 61000-4-12
Insulation resistance:
IEC 60255-5
Dielectric strength:
IEC 60255-6
ANSI/IEEE C37.90
Electrostatic discharge: EN 61000-4-2
Surge immunity:
EN 61000-4-5
RFI susceptibility:
ANSI/IEEE C37.90.2
IEC 61000-4-3
IEC 60255-22-3
Ontario Hydro C-5047-77
Conducted RFI:
IEC 61000-4-6
Voltage dips/interruptions/variations:
IEC 61000-4-11
IEC 60255-11
Power frequency magnetic field immunity:
IEC 61000-4-8
Pulse magnetic field immunity: IEC 61000-4-9
Vibration test (sinusoidal): IEC 60255-21-1
Shock and bump:
IEC 60255-21-2
Seismic:
IEC 60255-21-3
IEEE C37.98
Cold:
IEC 60028-2-1, 16 h at –40°C
Dry heat:
IEC 60028-2-2, 16 h at 85°C
Type test report available upon request.
2.2.12 PRODUCTION TESTS
THERMAL
Products go through an environmental test based upon an
Accepted Quality Level (AQL) sampling process.
2.2.13 APPROVALS
APPROVALS
UL Listed for the USA and Canada
CE:
LVD 73/23/EEC:
IEC 1010-1
EMC 81/336/EEC:
EN 50081-2, EN 50082-2
2.2.14 MAINTENANCE
MOUNTING
Attach mounting brackets using 20 inch-pounds (±2 inch-pounds)
of torque.
CLEANING
Normally, cleaning is not required; but for situations where dust
has accumulated on the faceplate display, a dry cloth can be used.
Units that are stored in a de-energized state should be
powered up once per year, for one hour continuously, to
avoid deterioration of electrolytic capacitors.
NOTE
NOTE
Содержание L60
Страница 2: ......
Страница 4: ......
Страница 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Страница 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 78: ...3 36 L60 Line Phase Comparison Relay GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3...
Страница 368: ...8 28 L60 Line Phase Comparison Relay GE Multilin 8 2 SINGLE POLE TRIPPING 8 THEORY OF OPERATION 8...
Страница 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Страница 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Страница 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...