Power System (Read/Write Setting)
4600
Nominal Frequency
25 to 60
Hz
1
F001
60
4601
Phase Rotation
0 to 1
---
1
F106
0 (ABC)
4602
Frequency And Phase Reference
0 to 5
---
1
F167
0 (SRC 1)
4603
Frequency Tracking Function
0 to 1
---
1
F102
1 (Enabled)
Breaker Control (Read/Write Setting) (2 modules)
4700
Breaker 1 Function
0 to 1
---
1
F102
0 (Disabled)
4701
Breaker 1 Name
---
---
---
F206
“Bkr 1"
4704
Breaker 1 Mode
0 to 1
---
1
F157
0 (3-Pole)
4705
Breaker 1 Open
0 to 65535
---
1
F300
0
4706
Breaker 1 Close
0 to 65535
---
1
F300
0
4707
Breaker 1 Phase A 3 Pole
0 to 65535
---
1
F300
0
4708
Breaker 1 Phase B
0 to 65535
---
1
F300
0
4709
Breaker 1 Phase C
0 to 65535
---
1
F300
0
470A
Breaker 1 External Alarm
0 to 65535
---
1
F300
0
470B
Breaker 1 Alarm Delay
0 to 1000000
s
0.001
F003
0
470D
Breaker 1 Push Button Control
0 to 1
---
1
F102
0 (Disabled)
470E
Breaker 1 Manual Close Recall Time
0 to 1000000
s
0.001
F003
0
4710
Breaker 1 Out Of Service
0 to 65535
---
1
F300
0
4711
Breaker 1 IEC 61850 XCBR.ST.Loc Status operand
0 to 65535
---
1
F300
0
4712
Reserved (6 items)
0 to 65535
s
1
F001
0
4718
...Repeated for Breaker 2
Synchrocheck (Read/Write Setting) (2 modules)
4780
Synchrocheck 1 Function
0 to 1
---
1
F102
0 (Disabled)
4781
Synchrocheck 1 V1 Source
0 to 5
---
1
F167
0 (SRC 1)
4782
Synchrocheck 1 V2 Source
0 to 5
---
1
F167
1 (SRC 2)
4783
Synchrocheck 1 Maximum Voltage Difference
0 to 400000
V
1
F060
10000
4785
Synchrocheck 1 Maximum Angle Difference
0 to 100
degrees
1
F001
30
4786
Synchrocheck 1 Maximum Frequency Difference
0 to 2
Hz
0.01
F001
100
4787
Synchrocheck 1 Dead Source Select
0 to 5
---
1
F176
1 (LV1 and DV2)
4788
Synchrocheck 1 Dead V1 Maximum Voltage
0 to 1.25
pu
0.01
F001
30
4789
Synchrocheck 1 Dead V2 Maximum Voltage
0 to 1.25
pu
0.01
F001
30
478A
Synchrocheck 1 Live V1 Minimum Voltage
0 to 1.25
pu
0.01
F001
70
478B
Synchrocheck 1 Live V2 Minimum Voltage
0 to 1.25
pu
0.01
F001
70
478C
Synchrocheck 1 Target
0 to 2
---
1
F109
0 (Self-reset)
478D
Synchrocheck 1 Events
0 to 1
---
1
F102
0 (Disabled)
478E
Synchrocheck 1 Block
0 to 65535
---
1
F300
0
478F
Synchrocheck 1 Frequency Hysteresis
0 to 0.1
Hz
0.01
F001
6
4790
...Repeated for Synchrocheck 2
Flexcurves A and B (Read/Write Settings)
4800
FlexCurve A (120 items)
0 to 65535
ms
1
F011
0
48F0
FlexCurve B (120 items)
0 to 65535
ms
1
F011
0
Modbus User Map (Read/Write Setting)
4A00
Modbus Address Settings for User Map (256 items)
0 to 65535
---
1
F001
0
User Displays Settings (Read/Write Setting) (16 modules)
4C00
User-Definable Display 1 Top Line Text
---
---
---
F202
“ “
4C0A
User-Definable Display 1 Bottom Line Text
---
---
---
F202
““
4C14
Modbus Addresses of Display 1 Items (5 items)
0 to 65535
---
1
F001
0
4C19
Reserved (7 items)
---
---
---
F001
0
Table B–9: MODBUS MEMORY MAP (Sheet 14 of 47)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание L60
Страница 2: ......
Страница 4: ......
Страница 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Страница 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 78: ...3 36 L60 Line Phase Comparison Relay GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3...
Страница 368: ...8 28 L60 Line Phase Comparison Relay GE Multilin 8 2 SINGLE POLE TRIPPING 8 THEORY OF OPERATION 8...
Страница 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Страница 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Страница 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...