L60 Line Phase Comparison Relay
GE Multilin
7.2 TARGETS
7 COMMANDS AND TARGETS
7
Table 7–2: MAJOR SELF-TEST ERROR MESSAGES
SELF-TEST ERROR
MESSAGE
LATCHED
TARGET
MESSAGE?
DESCRIPTION OF PROBLEM
HOW OFTEN THE
TEST IS PERFORMED
WHAT TO DO
DSP ERRORS:
A/D Calibration, A/D
Interrupt, A/D Reset, Inter
DSP Rx, Sample Int, Rx
Interrupt, Tx Interrupt, Rx
Sample Index, Invalid
Settings, Rx Checksum
Yes
CT/VT module with digital signal
processor may have a problem.
Every 1/8th of a cycle.
Cycle the control power (if the problem
recurs, contact the factory).
DSP ERROR:
INVALID REVISION
Yes
One or more DSP modules in a
multiple DSP unit has Rev. C
hardware
Rev. C DSP needs to be replaced
with a Rev. D DSP.
Contact the factory
EQUIPMENT MISMATCH
with 2nd-line detail
No
Configuration of modules does not
match the order code stored in the
CPU.
On power up; thereafter, the
backplane is checked for missing
cards every 5 seconds.
Check all modules against the order
code, ensure they are inserted
properly, and cycle control power (if
problem persists, contact factory).
FLEXLOGIC ERR TOKEN
with 2nd-line detail
No
FlexLogic™ equations do not
compile properly.
Event driven; whenever Flex-
Logic™ equations are modified.
Finish all equation editing and use self
test to debug any errors.
LATCHING OUTPUT
ERROR
No
Discrepancy in the position of a
latching contact between firmware
and hardware has been detected.
Every 1/8th of a cycle.
The latching output module failed.
Replace the Module.
PROGRAM MEMORY
Test Failed
Yes
Error was found while checking
Flash memory.
Once flash is uploaded with new
firmware.
Contact the factory.
UNIT NOT CALIBRATED
No
Settings indicate the unit is not
calibrated.
On power up.
Contact the factory.
UNIT NOT PROGRAMMED No
PRODUCT SETUP
INSTALLATION
setting indicates
relay is not in a programmed state.
On power up and whenever the
RELAY PROGRAMMED
setting is
altered.
Program all settings (especially those
under
PRODUCT SETUP
INSTALLATION
).
Table 7–3: MINOR SELF-TEST ERROR MESSAGES
SELF-TEST ERROR
MESSAGE
LATCHED
TARGET
MESSAGE
DESCRIPTION OF PROBLEM
HOW OFTEN THE
TEST IS PERFORMED
WHAT TO DO
BATTERY FAIL
Yes
Battery is not functioning.
Monitored every 5 seconds. Reported
after 1 minute if problem persists.
Replace the battery located in the
power supply module (1H or 1L).
DIRECT RING BREAK
No
Direct input/output settings
configured for a ring, but the
connection is not in a ring.
Every second.
Check direct input/output configuration
and/or wiring.
DIRECT DEVICE OFF
No
A direct device is configured but
not connected.
Every second.
Check direct input/output configuration
and/or wiring.
EEPROM DATA
ERROR
Yes
The non-volatile memory has been
corrupted.
On power up only.
If this message appears after an order
code update is preformed, press the
RESET key to clear target message. In
other cases, contact the factory.
IRIG-B FAILURE
No
A bad IRIG-B input signal has been
detected
Monitored whenever an IRIG-B signal
is received.
Ensure the IRIG-B cable is connected,
check cable functionality (i.e. look for
physical damage or perform continuity
test), ensure IRIG-B receiver is
functioning, and check input signal level
(it may be less than specification). If
none of these apply, contact the factory.
LATCHING OUT
ERROR
Yes
Latching output failure.
Event driven.
Contact the factory.
LOW ON MEMORY
Yes
Memory is close to 100% capacity. Monitored every 5 seconds.
Contact the factory.
PRI ETHERNET FAIL
Yes
Primary Ethernet connection failed. Monitored every 2 seconds
Check connections.
PROTOTYPE
FIRMWARE
Yes
A prototype version of the firmware
is loaded.
On power up only.
Contact the factory.
REMOTE DEVICE OFF No
One or more GOOSE devices are
not responding.
Event driven – occurs when a device
programmed to receive GOOSE
messages stops receiving. Every 1 to
60 s, depending on GOOSE packets.
Check GOOSE setup.
SEC ETHERNET FAIL
Yes
Sec. Ethernet connection failed.
Monitored every 2 seconds
Check connections.
SNTP FAILURE
No
SNTP server not responding.
10 to 60 seconds.
Check SNTP configuration and/or
network connections.
SYSTEM EXCEPTION
Yes
Abnormal restart from modules
being removed/inserted when
powered-up, abnormal DC supply,
or internal relay failure.
Event driven.
Contact the factory.
WATCHDOG ERROR
No
Some tasks are behind schedule.
Event driven.
Contact the factory.
Содержание L60
Страница 2: ......
Страница 4: ......
Страница 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Страница 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 78: ...3 36 L60 Line Phase Comparison Relay GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3...
Страница 368: ...8 28 L60 Line Phase Comparison Relay GE Multilin 8 2 SINGLE POLE TRIPPING 8 THEORY OF OPERATION 8...
Страница 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Страница 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Страница 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...