GE Multilin
L60 Line Phase Comparison Relay
5-205
5 SETTINGS
5.7 INPUTS/OUTPUTS
5
5.7.2 VIRTUAL INPUTS
PATH: SETTINGS
INPUTS/OUTPUTS
VIRTUAL INPUTS VIRTUAL INPUT 1(64)
There are 64 virtual inputs that can be individually programmed to respond to input signals from the keypad (Commands
menu) and communications protocols. All virtual input operands are defaulted to OFF = 0 unless the appropriate input sig-
nal is received.
Virtual input states are preserved through a control power loss
.
If the
VIRTUAL INPUT x FUNCTION
is to “Disabled”, the input will be forced to 'Off' (Logic 0) regardless of any attempt to alter
the input. If set to “Enabled”, the input operates as shown on the logic diagram and generates output FlexLogic™ operands
in response to received input signals and the applied settings.
There are two types of operation: Self-Reset and Latched. If
VIRTUAL INPUT x TYPE
is “Self-Reset”, when the input signal
transits from OFF = 0 to ON = 1, the output operand will be set to ON = 1 for only one evaluation of the FlexLogic™ equa-
tions and then return to OFF = 0. If set to “Latched”, the virtual input sets the state of the output operand to the same state
as the most recent received input, ON =1 or OFF = 0.
The “Self-Reset” operating mode generates the output operand for a single evaluation of the FlexLogic™
equations. If the operand is to be used anywhere other than internally in a FlexLogic™ equation, it will
likely have to be lengthened in time. A FlexLogic™ timer with a delayed reset can perform this function.
Figure 5–116: VIRTUAL INPUTS SCHEME LOGIC
VIRTUAL INPUT
1
VIRTUAL INPUT
1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
VIRTUAL INPUT
1 ID:
Virt Ip 1
Range: Up to 12 alphanumeric characters
MESSAGE
VIRTUAL INPUT
1
TYPE: Latched
Range: Self-Reset, Latched
MESSAGE
VIRTUAL INPUT
1
EVENTS: Disabled
Range: Disabled, Enabled
NOTE
VIRTUAL INPUT 1
FUNCTION:
VIRTUAL INPUT 1 ID:
“Virtual Input 1 to OFF = 0”
“Virtual Input 1 to ON = 1”
AND
AND
AND
OR
SETTING
SETTING
Enabled=1
Disabled=0
(Flexlogic Operand)
Virt Ip 1
827080A2.CDR
SETTING
VIRTUAL INPUT 1
TYPE:
Latched
Self - Reset
R
S
Latch
Содержание L60
Страница 2: ......
Страница 4: ......
Страница 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Страница 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 78: ...3 36 L60 Line Phase Comparison Relay GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3...
Страница 368: ...8 28 L60 Line Phase Comparison Relay GE Multilin 8 2 SINGLE POLE TRIPPING 8 THEORY OF OPERATION 8...
Страница 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Страница 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Страница 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...