5-188
L60 Line Phase Comparison Relay
GE Multilin
5.6 CONTROL ELEMENTS
5 SETTINGS
5
5.6.9 PILOT SCHEMES
a) PERMISSIVE OVERREACHING TRANSFER TRIP (POTT)
PATH: SETTINGS
CONTROL ELEMENTS
PILOT SCHEMES
POTT SCHEME
This scheme is intended for two-terminal line applications only. It uses an over-reaching Zone 2 distance element to essen-
tially compare the direction to a fault at both the ends of the line. Ground directional overcurrent functions available in the
relay can be used in conjunction with the Zone 2 distance element to key the scheme and initiate its operation. This pro-
vides increased coverage for high-resistance faults.
For proper scheme operation, the Zone 2 phase and ground distance elements must be enabled, configured, and set per
the rules of distance relaying. The Line Pickup element should be enabled, configured and set properly to detect line-end-
open/weak-infeed conditions. If used by this scheme, the selected ground directional overcurrent function(s) must be
enabled, configured, and set accordingly.
•
POTT PERMISSIVE ECHO:
If set to "Enabled" this setting will result in sending a permissive echo signal to the remote
end. The permissive signal is echoed back upon receiving a reliable POTT RX signal from the remote end while the
line-end-open condition is identified by the Line Pickup logic. The Permissive Echo is programmed as a one-shot logic.
The echo is sent only once and then the echo logic locks out for a settable period of time (
ECHO LOCKOUT
setting). The
duration of the echo pulse does not depend on the duration or shape of the received POTT RX signal but is settable as
ECHO DURATION
.
•
POTT RX PICKUP DELAY:
This setting enables the relay to cope with spurious receive signals. The delay should be
set longer than the longest spurious TX signal that can occur simultaneously with the zone 2 pickup. The selected
delay will increase the response time of the scheme.
•
TRANS BLOCK PICKUP DELAY:
This setting defines a transient blocking mechanism embedded in the POTT
scheme for coping with the exposure of a ground directional overcurrent function (if used) to current reversal condi-
tions. The transient blocking mechanism applies to the ground overcurrent path only as the reach settings for the zone
2 distance functions is not expected to be long for two-terminal applications, and the security of the distance functions
is not endangered by the current reversal conditions. Upon receiving the POTT RX signal, the transient blocking mech-
anism allows the RX signal to be passed and aligned with the
GND DIR O/C FWD
indication only for a period of time
POTT SCHEME
POTT SCHEME
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
POTT PERMISSIVE
ECHO: Disabled
Range: Disabled, Enabled
MESSAGE
POTT RX PICKUP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
TRANS BLOCK PICKUP
DELAY: 0.020 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
TRANS BLOCK RESET
DELAY: 0.090 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
ECHO DURATION:
0.100 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
ECHO LOCKOUT:
0.250 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
LINE END OPEN PICKUP
DELAY: 0.050
s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
POTT SEAL-IN
DELAY: 0.400
s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
GND DIR O/C FWD:
Off
Range: FlexLogic™ operand
MESSAGE
POTT RX:
Off
Range: FlexLogic™ operand
Содержание L60
Страница 2: ......
Страница 4: ......
Страница 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Страница 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 78: ...3 36 L60 Line Phase Comparison Relay GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3...
Страница 368: ...8 28 L60 Line Phase Comparison Relay GE Multilin 8 2 SINGLE POLE TRIPPING 8 THEORY OF OPERATION 8...
Страница 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Страница 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Страница 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...