GE Multilin
L60 Line Phase Comparison Relay
5-185
5 SETTINGS
5.6 CONTROL ELEMENTS
5
e) VT FUSE FAILURE
PATH: SETTINGS
CONTROL ELEMENTS
MONITORING ELEMENTS
VT FUSE FAILURE 1(2)
Every signal source includes a fuse failure scheme.
The VT fuse failure detector can be used to raise an alarm and/or block elements that may operate incorrectly for a full or
partial loss of AC potential caused by one or more blown fuses. Some elements that might be blocked (via the BLOCK
input) are distance, voltage restrained overcurrent, and directional current.
There are two classes of fuse failure that may occur:
Class A: Loss of one or two phases.
Class B: Loss of all three phases.
Different means of detection are required for each class. An indication of Class A failures is a significant level of negative
sequence voltage, whereas an indication of Class B failures is when positive sequence current is present and there is an
insignificant amount of positive sequence voltage. These noted indications of fuse failure could also be present when faults
are present on the system, so a means of detecting faults and inhibiting fuse failure declarations during these events is pro-
vided. Once the fuse failure condition is declared, it will be sealed-in until the cause that generated it disappears.
An additional condition is introduced to inhibit a fuse failure declaration when the monitored circuit is de-energized; positive
sequence voltage and current are both below threshold levels.
The
VT FUSE FAILURE 1(2) FUNCTION
setting enables/disables the fuse failure feature for each source.
Figure 5–108: VT FUSE FAIL SCHEME LOGIC
VT FUSE FAILURE 1
VT FUSE FAILURE 1
FUNCTION: Disabled
Range: Disabled, Enabled
827093AH.CDR
VT FUSE FAILURE
FUNCTION:
V_2 > 0.15 p.u.
V_1 < 0.05 p.u.
V_1 < 0.7 p.u.
I_1 > 0.075 p.u.
I_1 < 0.05 p.u.
RUN
RUN
RUN
RUN
RUN
SETTING
COMPARATORS
SOURCE 1
FLEXLOGIC OPERANDS
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
Disabled=0
Enabled=1
SRC1 VT FUSE FAIL OP
SRC1 VT FUSE FAIL VOL LOSS
SRC1 VT FUSE FAIL DPO
FUSE
FAIL
FAULT
SRC1 50DD OP
OPEN POLE OP
D60, L60 only
AND
AND
AND
AND
SET
RESET
Reset-dominant
LATCH
AND
AND
AND
AND
AND
OR
OR
OR
OR
V_1
I_1
V_2
20 CYCLES
2 CYCLES
LATCH
SET
Reset-dominant
RESET
Содержание L60
Страница 2: ......
Страница 4: ......
Страница 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Страница 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 78: ...3 36 L60 Line Phase Comparison Relay GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3...
Страница 368: ...8 28 L60 Line Phase Comparison Relay GE Multilin 8 2 SINGLE POLE TRIPPING 8 THEORY OF OPERATION 8...
Страница 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Страница 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Страница 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...