GE Multilin
L60 Line Phase Comparison Relay
5-157
5 SETTINGS
5.6 CONTROL ELEMENTS
5
5.6CONTROL ELEMENTS
5.6.1 OVERVIEW
Control elements are generally used for control rather than protection. See the
Introduction to Elements
section at the
beginning of this chapter for further information.
5.6.2 SETTING GROUPS
PATH: SETTINGS
CONTROL ELEMENTS SETTINGS GROUPS
The Setting Groups menu controls the activation/deactivation of up to six possible groups of settings in the
GROUPED ELE-
MENTS
settings menu. The faceplate ‘Settings In Use’ LEDs indicate which active group (with a non-flashing energized
LED) is in service.
The
SETTING GROUPS BLK
setting prevents the active setting group from changing when the FlexLogic™ parameter is set to
"On". This can be useful in applications where it is undesirable to change the settings under certain conditions, such as the
breaker being open.
Each
GROUP n ACTIVATE ON
setting selects a FlexLogic™ operand which, when set, will make the particular setting group
active for use by any grouped element. A priority scheme ensures that only one group is active at a given time – the high-
est-numbered group which is activated by its
GROUP n ACTIVATE ON
parameter takes priority over the lower-numbered
groups. There is no “activate on” setting for Group 1 (the default active group), because Group 1 automatically becomes
active if no other group is active.
The
SETTING GROUP 1(6) NAME
settings allows to user to assign a name to each of the six settings groups. Once pro-
grammed, this name will appear on the second line of the
GROUPED ELEMENTS SETTING GROUP 1(6)
menu display.
The relay can be set up via a FlexLogic™ equation to receive requests to activate or de-activate a particular non-default
settings group. The following FlexLogic™ equation (see the figure below) illustrates requests via remote communications
(e.g.
VIRTUAL INPUT 1
) or from a local contact input (e.g. H7a) to initiate the use of a particular settings group, and requests
from several overcurrent pickup measuring elements to inhibit the use of the particular settings group. The assigned
VIR-
TUAL OUTPUT 1
operand is used to control the “On” state of a particular settings group.
SETTING GROUPS
SETTING GROUPS
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
SETTING GROUPS BLK:
Off
Range: FlexLogic™ operand
MESSAGE
GROUP 2 ACTIVATE ON:
Off
Range: FlexLogic™ operand
MESSAGE
GROUP 3 ACTIVATE ON:
Off
Range: FlexLogic™ operand
↓
MESSAGE
GROUP 6 ACTIVATE ON:
Off
Range: FlexLogic™ operand
MESSAGE
GROUP 1 NAME:
Range: up to 16 alphanumeric characters
MESSAGE
GROUP 2 NAME:
Range: up to 16 alphanumeric characters
↓
MESSAGE
GROUP 6 NAME:
Range: up to 16 alphanumeric characters
MESSAGE
SETTING GROUP
EVENTS: Disabled
Range: Disabled, Enabled
Содержание L60
Страница 2: ......
Страница 4: ......
Страница 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Страница 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 78: ...3 36 L60 Line Phase Comparison Relay GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3...
Страница 368: ...8 28 L60 Line Phase Comparison Relay GE Multilin 8 2 SINGLE POLE TRIPPING 8 THEORY OF OPERATION 8...
Страница 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Страница 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Страница 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...