GE Multilin
L60 Line Phase Comparison Relay
5-89
5 SETTINGS
5.5 GROUPED ELEMENTS
5
The
FORCE SELF-POLAR
and
FORCE MEM-POLAR
settings should never be asserted simultaneously. If this happens, the logic
will give higher priority to forcing self-polarization as indicated in the logic below. This is consistent with the overall philoso-
phy of distance memory polarization: the memory polarization cannot be applied permanently but for a limited time only; the
self-polarization may be applied permanently and therefore should take higher priority.
The distance zones of the L60 is are identical to that of the UR-series D60 Line Distance Relay. For additional infor-
mation on the L60 distance functions, please refer to Chapter 8 of the D60 manual, available on the EnerVista CD
or free of charge on the GE Multilin web page.
Figure 5–40: MEMORY VOLTAGE LOGIC
b) PHASE DISTANCE
PATH: SETTINGS
GROUPED ELEMENTS SETTING GROUP 1(6)
DISTANCE
PHASE DISTANCE Z1(Z3)
PHASE DISTANCE Z1
PHS DIST Z1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
PHS DIST Z1 DIR:
Forward
Range: Forward, Reverse, Non-directional
MESSAGE
PHS DIST Z1
SHAPE: Mho
Range: Mho, Quad
MESSAGE
PHS DIST Z1 XFMR VOL
CONNECTION: None
Range: None, Dy1, Dy3, Dy5, Dy7, Dy9, Dy11, Yd1, Yd3,
Yd5, Yd7, Yd9, Yd11
MESSAGE
PHS DIST Z1 XFMR CUR
CONNECTION: None
Range: None, Dy1, Dy3, Dy5, Dy7, Dy9, Dy11, Yd1, Yd3,
Yd5, Yd7, Yd9, Yd11
MESSAGE
PHS DIST Z1
REACH: 2.00
ohms
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
PHS DIST Z1
RCA: 85°
Range: 30 to 90° in steps of 1
MESSAGE
PHS DIST Z1 REV
REACH: 2.00 ohms
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
PHS DIST Z1 REV
REACH RCA: 85°
Range: 30 to 90° in steps of 1
MESSAGE
PHS DIST Z1
COMP LIMIT: 90
°
Range: 30 to 90° in steps of 1
MESSAGE
PHS DIST Z1
DIR RCA: 85°
Range: 30 to 90° in steps of 1
NOTE
827842A6.CDR
DISTANCE SOURCE:
FORCE SELF-POLAR:
MEMORY DURATION:
Use V_1
Use V_1 mem
AND
OR
AND
AND
AND
OR
S Q
R
SETTING
SETTING
SETTING
I
A
V_B, V_RMS_B
I
A < 0.05 pu
I
B
V_C, V_RMS_C
I
B < 0.05 pu
I
C
I
C < 0.05 pu
V_RMS- V < V_RMS/8
V_RMS- V < V_RMS/8
V_RMS- V < V_RMS/8
V_1
V_A, V_RMS_A
Off=0
V_1 > 0.8 pu
V_1 < 1.15 pu
V_1 < 0.1 pu
5 cy
RUN
UPDATE MEMORY
0
0
t
RST
FORCE MEM-POLAR:
SETTING
Off=0
AND
AND
Содержание L60
Страница 2: ......
Страница 4: ......
Страница 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Страница 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 78: ...3 36 L60 Line Phase Comparison Relay GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3...
Страница 368: ...8 28 L60 Line Phase Comparison Relay GE Multilin 8 2 SINGLE POLE TRIPPING 8 THEORY OF OPERATION 8...
Страница 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Страница 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Страница 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...