5-32
L60 Line Phase Comparison Relay
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
5.2.13 USER-PROGRAMMABLE PUSHBUTTONS
PATH: SETTINGS PRODUCT SETUP
USER-PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1(12)
The L60 has 12 optional user-programmable pushbuttons available, each configured via 12 identical menus. The pushbut-
tons provide an easy and error-free method of manually entering digital information (On, Off) into FlexLogic™ equations as
well as protection and control elements. Typical applications include breaker control, autorecloser blocking, ground protec-
tion blocking, and setting groups changes.
The user-configurable pushbuttons are shown below. They can be custom labeled with a factory-provided template, avail-
able online at
.
Figure 5–5: USER-PROGRAMMABLE PUSHBUTTONS
Each pushbutton asserts its own On and Off FlexLogic™ operands, respectively. FlexLogic™ operands should be used to
program desired pushbutton actions. The operand names are
PUSHBUTTON 1 ON
and
PUSHBUTTON 1 OFF
.
A pushbutton may be programmed to latch or self-reset. An indicating LED next to each pushbutton signals the present sta-
tus of the corresponding "On" FlexLogic™ operand. When set to "Latched", the state of each pushbutton is stored in non-
volatile memory which is maintained during any supply power loss.
Pushbuttons states can be logged by the Event Recorder and displayed as target messages. User-defined messages can
also be associated with each pushbutton and displayed when the pushbutton is ON.
•
PUSHBUTTON 1 FUNCTION:
This setting selects the characteristic of the pushbutton. If set to “Disabled”, the push-
button is deactivated and the corresponding FlexLogic™ operands (both “On” and “Off”) are de-asserted. If set to
“Self-reset”, the control logic of the pushbutton asserts the “On” corresponding FlexLogic™ operand as long as the
pushbutton is being pressed. As soon as the pushbutton is released, the FlexLogic™ operand is de-asserted. The
“Off” operand is asserted/de-asserted accordingly.
If set to “Latched”, the control logic alternates the state of the corresponding FlexLogic™ operand between “On” and
“Off” on each push of the button. When operating in “Latched” mode, FlexLogic™ operand states are stored in non-vol-
atile memory. Should power be lost, the correct pushbutton state is retained upon subsequent power up of the relay.
USER PUSHBUTTON 1
PUSHBUTTON 1
FUNCTION: Disabled
Range: Self-Reset, Latched, Disabled
MESSAGE
PUSHBTN 1 ID TEXT:
Range: Up to 20 alphanumeric characters
MESSAGE
PUSHBTN 1 ON TEXT:
Range: Up to 20 alphanumeric characters
MESSAGE
PUSHBTN 1 OFF TEXT:
Range: Up to 20 alphanumeric characters
MESSAGE
PUSHBTN 1 DROP-OUT
TIME: 0.00 s
Range: 0 to 60.00 s in steps of 0.01
MESSAGE
PUSHBUTTON 1
TARGETS: Disabled
Range: Self-Reset, Latched, Disabled
MESSAGE
PUSHBUTTON 1
EVENTS: Disabled
Range: Disabled, Enabled
USER LABEL
USER LABEL
USER LABEL
USER LABEL
USER LABEL
USER LABEL
7
9
11
8
10
12
USER LABEL
1
3
5
2
4
6
USER LABEL
USER LABEL
USER LABEL
USER LABEL
USER LABEL
Содержание L60
Страница 2: ......
Страница 4: ......
Страница 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Страница 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 78: ...3 36 L60 Line Phase Comparison Relay GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3...
Страница 368: ...8 28 L60 Line Phase Comparison Relay GE Multilin 8 2 SINGLE POLE TRIPPING 8 THEORY OF OPERATION 8...
Страница 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Страница 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Страница 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...