GE Multilin
L60 Line Phase Comparison Relay
5-31
5 SETTINGS
5.2 PRODUCT SETUP
5
5.2.12 CONTROL PUSHBUTTONS
PATH: SETTINGS PRODUCT SETUP
CONTROL PUSHBUTTONS CONTROL PUSHBUTTON 1(7)
The three standard pushbuttons located on the top left panel of the faceplate are user-programmable and can be used for
various applications such as performing an LED test, switching setting groups, and invoking and scrolling though user-pro-
grammable displays, etc. Firmware revisions 3.2x and older use these three pushbuttons for manual breaker control. This
functionality has been retained – if the Breaker Control feature is configured to use the three pushbuttons, they cannot be
used as user-programmable control pushbuttons. The location of the control pushbuttons in the following figure.
An additonal four control pushbuttons are included when the L60 is ordered with twelve user programmable pushbuttons.
Figure 5–3: CONTROL PUSHBUTTONS
Control pushbuttons are not typically used for critical operations and are not protected by the control password. However,
by supervising their output operands, the user can dynamically enable or disable control pushbuttons for security reasons.
Each control pushbutton asserts its own FlexLogic™ operand,
CONTROL PUSHBTN 1(7) ON
. These operands should be
configured appropriately to perform the desired function. The operand remains asserted as long as the pushbutton is
pressed and resets when the pushbutton is released. A dropout delay of 100 ms is incorporated to ensure fast pushbutton
manipulation will be recognized by various features that may use control pushbuttons as inputs.
An event is logged in the Event Record (as per user setting) when a control pushbutton is pressed; no event is logged when
the pushbutton is released. The faceplate keys (including control keys) cannot be operated simultaneously – a given key
must be released before the next one can be pressed.
The control pushbuttons become user-programmable only if the Breaker Control feature is not configured for manual con-
trol via the User 1 through 3 pushbuttons as shown below. If configured for manual control, Breaker Control typically uses
the larger, optional user-programmable pushbuttons, making the control pushbuttons available for other user applications.
Figure 5–4: CONTROL PUSHBUTTON LOGIC
CONTROL
PUSHBUTTON 1
CONTROL PUSHBUTTON 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
CONTROL PUSHBUTTON 1
EVENTS: Disabled
Range: Disabled, Enabled
842733A2.CDR
PICKUP
ALARM
TRIP
TEST MODE
TROUBLE
IN SERVICE
STATUS
USER 3
USER 2
USER 1
RESET
EVENT CAUSE
NEUTRAL/GROUND
PHASE C
PHASE B
PHASE A
OTHER
FREQUENCY
CURRENT
VOLTAGE
THREE
STANDARD
CONTROL
PUSHBUTTONS
USER 7
USER 6
USER 5
USER 4
FOUR EXTRA
OPTIONAL
CONTROL
PUSHBUTTONS
842010A2.CDR
CONTROL PUSHBUTTON
1 FUNCTION:
SYSTEM SETUP/
BREAKERS/BREAKER 1/
BREAKER 1 PUSHBUTTON
:
CONTROL
SYSTEM SETUP/
BREAKERS/BREAKER 2/
BREAKER 2 PUSHBUTTON
:
CONTROL
SETTING
SETTINGS
TIMER
FLEXLOGIC OPERAND
Enabled=1
Enabled=1
When applicable
Enabled=1
RUN
OFF
ON
AND
100 msec
0
CONTROL PUSHBTN 1 ON
{
Содержание L60
Страница 2: ......
Страница 4: ......
Страница 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Страница 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 78: ...3 36 L60 Line Phase Comparison Relay GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3...
Страница 368: ...8 28 L60 Line Phase Comparison Relay GE Multilin 8 2 SINGLE POLE TRIPPING 8 THEORY OF OPERATION 8...
Страница 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Страница 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Страница 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...