5-30
L60 Line Phase Comparison Relay
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
Refer to the
Control of Setting Groups
example in the
Control Elements
section of this chapter for group activation.
5.2.11 USER-PROGRAMMABLE SELF TESTS
PATH: SETTINGS PRODUCT SETUP
USER-PROGRAMMABLE SELF TESTS
All major self-test alarms are reported automatically with their corresponding FlexLogic™ operands, events, and targets.
Most of the Minor Alarms can be disabled if desired.
When in the “Disabled” mode, minor alarms will not assert a FlexLogic™ operand, write to the event recorder, display target
messages. Moreover, they will not trigger the
ANY MINOR ALARM
or
ANY SELF-TEST
messages. When in the “Enabled” mode,
minor alarms continue to function along with other major and minor alarms. Refer to the
Relay Self-Tests
section in Chapter
7 for additional information on major and minor self-test alarms.
Table 5–4: RECOMMENDED SETTINGS FOR LED PANEL 2 LABELS
SETTING
PARAMETER
SETTING
PARAMETER
LED 1 Operand
SETTING GROUP ACT 1
LED 13 Operand
Off
LED 2 Operand
SETTING GROUP ACT 2
LED 14 Operand
BREAKER 2 OPEN
LED 3 Operand
SETTING GROUP ACT 3
LED 15 Operand
BREAKER 2 CLOSED
LED 4 Operand
SETTING GROUP ACT 4
LED 16 Operand
BREAKER 2 TROUBLE
LED 5 Operand
SETTING GROUP ACT 5
LED 17 Operand
SYNC 1 SYNC OP
LED 6 Operand
SETTING GROUP ACT 6
LED 18 Operand
SYNC 2 SYNC OP
LED 7 Operand
Off
LED 19 Operand
Off
LED 8 Operand
Off
LED 20 Operand
Off
LED 9 Operand
BREAKER 1 OPEN
LED 21 Operand
AR ENABLED
LED 10 Operand
BREAKER 1 CLOSED
LED 22 Operand
AR DISABLED
LED 11 Operand
BREAKER 1 TROUBLE
LED 23 Operand
AR RIP
LED 12 Operand
Off
LED 24 Operand
AR LO
USER-PROGRAMMABLE
SELF TESTS
DIRECT RING BREAK
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
MESSAGE
DIRECT DEVICE OFF
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
MESSAGE
REMOTE DEVICE OFF
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units that contain a
CPU with Ethernet capability.
MESSAGE
PRI. ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled. Valid for units that contain a
CPU with a primary fiber port.
MESSAGE
SEC. ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled. Valid for units that contain a
CPU with a redundant fiber port.
MESSAGE
BATTERY FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
SNTP FAIL
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units that contain a
CPU with Ethernet capability.
MESSAGE
IRIG-B FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
Содержание L60
Страница 2: ......
Страница 4: ......
Страница 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Страница 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 78: ...3 36 L60 Line Phase Comparison Relay GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3...
Страница 368: ...8 28 L60 Line Phase Comparison Relay GE Multilin 8 2 SINGLE POLE TRIPPING 8 THEORY OF OPERATION 8...
Страница 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Страница 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Страница 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...