5.2 PRODUCT SETUP
5
The L60 supports the Distributed Network Protocol (DNP) version 3.0. The L60 can be used as a DNP slave device con-
nected to multiple DNP masters (usually an RTU or a SCADA master station). Since the L60 maintains two sets of DNP
data change buffers and connection information, two DNP masters can actively communicate with the L60 at one time.
The DNP Channels sub-menu is shown below.
PATH: SETTINGS PRODUCT SETUP
COMMUNICATIONS
DNP PROTOCOL DNP CHANNELS
The
DNP CHANNEL 1(2) PORT
settings select the communications port assigned to the DNP protocol for each channel. Once
DNP is assigned to a serial port, the Modbus protocol is disabled on that port. Note that COM1 can be used only in non-
Ethernet UR relays. When this setting is set to “Network - TCP”, the DNP protocol can be used over TCP/IP on channels 1
or 2. When this value is set to “Network - UDP”, the DNP protocol can be used over UDP/IP on channel 1 only. Refer to
Appendix E
for additional information on the DNP protocol.
Changes to the
DNP CHANNEL 1(2) PORT
settings will take effect only after power has been cycled to the relay.
The
DNP NETWORK CLIENT ADDRESS
settings can force the L60 to respond to a maximum of five specific DNP masters. The
settings in this sub-menu are shown below.
MESSAGE
DNP OBJECT 2
DEFAULT VARIATION: 2
Range: 1, 2
MESSAGE
DNP OBJECT 20
DEFAULT VARIATION: 1
Range: 1, 2, 5, 6
MESSAGE
DNP OBJECT 21
DEFAULT VARIATION: 1
Range: 1, 2, 9, 10
MESSAGE
DNP OBJECT 22
DEFAULT VARIATION: 1
Range: 1, 2, 5, 6
MESSAGE
DNP OBJECT 23
DEFAULT VARIATION: 2
Range: 1, 2, 5, 6
MESSAGE
DNP OBJECT 30
DEFAULT VARIATION: 1
Range: 1, 2, 3, 4, 5
MESSAGE
DNP OBJECT 32
DEFAULT VARIATION: 1
Range: 1, 2, 3, 4, 5, 7
MESSAGE
DNP NUMBER OF PAIRED
CONTROL POINTS: 0
Range: 0 to 32 in steps of 1
DNP CHANNELS
DNP CHANNEL 1 PORT:
NETWORK
Range: NONE, COM1 - RS485, COM2 - RS485,
FRONT PANEL - RS232, NETWORK - TCP,
NETWORK - UDP
MESSAGE
DNP CHANNEL 2 PORT:
COM2 - RS485
Range: NONE, COM1 - RS485, COM2 - RS485,
FRONT PANEL - RS232, NETWORK - TCP,
NETWORK - UDP
NOTE
Содержание L60
Страница 2: ......
Страница 4: ......
Страница 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Страница 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 78: ...3 36 L60 Line Phase Comparison Relay GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3...
Страница 368: ...8 28 L60 Line Phase Comparison Relay GE Multilin 8 2 SINGLE POLE TRIPPING 8 THEORY OF OPERATION 8...
Страница 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Страница 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Страница 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...