5.2.3 CLEAR RELAY RECORDS
PATH: SETTINGS PRODUCT SETUP
CLEAR RELAY RECORDS
Selected records can be cleared from user-programmable conditions with FlexLogic™ operands. Assigning user-program-
mable pushbuttons to clear specific records are typical applications for these commands. Since the L60 responds to rising
edges of the configured FlexLogic™ operands, they must be asserted for at least 50 ms to take effect.
Clearing records with user-programmable operands is not protected by the command password. However, user-program-
mable pushbuttons are protected by the command password. Thus, if they are used to clear records, the user-programma-
ble pushbuttons can provide extra security if required.
For example, to assign User-Programmable Pushbutton 1 to clear demand records, the following settings should be
applied.
1.
Assign the clear demand function to Pushbutton 1 by making the following change in the
SETTINGS PRODUCT SETUP
CLEAR RELAY RECORDS
menu:
CLEAR DEMAND:
“
PUSHBUTTON 1 ON
”
2.
Set the properties for User-Programmable Pushbutton 1 by making the following changes in the
SETTINGS PRODUCT
SETUP
USER-PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1
menu:
PUSHBUTTON 1 FUNCTION:
“Self-reset”
PUSHBTN 1 DROP-OUT TIME:
“0.20 s”
CLEAR RELAY
RECORDS
CLEAR FAULT REPORTS:
Off
Range: FlexLogic™ operand
MESSAGE
CLEAR EVENT RECORDS:
Off
Range: FlexLogic™ operand
MESSAGE
CLEAR OSCILLOGRAPHY?
No
Range: FlexLogic™ operand
MESSAGE
CLEAR DATA LOGGER:
Off
Range: FlexLogic™ operand
MESSAGE
CLEAR ARC AMPS 1:
Off
Range: FlexLogic™ operand
MESSAGE
CLEAR ARC AMPS 2:
Off
Range: FlexLogic™ operand
MESSAGE
RESET UNAUTH ACCESS:
Off
Range: FlexLogic™ operand
MESSAGE
CLEAR DIR I/O STATS:
Off
Range: FlexLogic™ operand.
Valid only for units with Direct I/O module.
Содержание L60
Страница 2: ......
Страница 4: ......
Страница 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Страница 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 78: ...3 36 L60 Line Phase Comparison Relay GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3...
Страница 368: ...8 28 L60 Line Phase Comparison Relay GE Multilin 8 2 SINGLE POLE TRIPPING 8 THEORY OF OPERATION 8...
Страница 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Страница 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Страница 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...