CHAPTER 7: COMMANDS AND TARGETS
TARGETS MENU
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
7-7
7
A target enables the EnerVista UR Setup software to monitor automatically and display the status of any active target
messages of all the devices inserted into that site.
Each L30 element with a TARGET setting has a target message that when activated by its element is displayed in sequence
with any other currently active target messages in the
TARGETS
menu. In the example shown, the Phase TOC4 and Digital
Element 48 target settings are active and so have their targets displayed. The down arrow below the two elements
indicates that there can be other active elements beyond these two.
For more information, see the description of target messages in the next section, and the Introduction to Elements section
in the Settings chapter for instructions on TARGET setting.
When no targets are active, the display reads
NO ACTIVE TARGETS
.
7.2.1 Target messages
When there are no active targets, the first target to become active causes the display to immediately default to that
message. If there are active targets and the user is navigating through other messages, and when the default message
timer times out (i.e. the keypad has not been used for a determined period of time), the display again defaults back to the
target message.
The range of variables for the target messages is described below. Phase information is included if applicable. If a target
message status changes, the status with the highest priority displays.
Table 7-1: Target message priority status
If a self test error is detected, a message appears indicating the cause of the error. For example UNIT NOT PROGRAMMED
indicates that the minimal relay settings have not been programmed.
7.2.2 Relay self-tests
7.2.2.1 Description
The relay performs a number of self-test diagnostic checks to ensure device integrity. The two types of self-tests (major
and minor) are listed in the following tables. When either type of error occurs, the Trouble LED Indicator turns on and a
target message displays. All errors record an event in the event recorder. Latched errors can be cleared by pressing the
RESET
key, providing the condition is no longer present.
Major self-test errors also result in the following:
•
The critical fail relay on the power supply module de-energizes
•
All other output relays de-energize and are prevented from further operation
•
The front panel In Service LED indicator turns off
•
A RELAY OUT OF SERVICE event is recorded
To view error messages in EnerVista software:
1.
Access
Actual Values > Records > Event Records
.
PHASE TOC4
OP: A B -
Displayed only if targets for this element are active.
Example shown.
DIGITAL ELEMENT 48:
LATCHED
Displayed only if targets for this element are active.
Example shown.
Priority
Active status
Description
1
OP
element operated and still picked up
2
PKP
element picked up and timed out
3
LATCHED
element had operated but has dropped out
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...