5-188
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
FLEXLOGIC
CHAPTER 5: SETTINGS
5
Table 5-24: L30 FlexLogic operands
Operand type
Operand syntax
Operand description
ANNUNCIATOR
Graphical front panel
ANY ANCTR ABNORMAL
ANY ANCTR ALARMED
On for one second when any annunciator window state changes from
normal to abnormal
On while any annunciator window state is abnormal
CONTROL
PUSHBUTTONS
Enhanced and
standard front panels
CONTROL PUSHBTN 1 ON
CONTROL PUSHBTN 2 ON
CONTROL PUSHBTN 3 ON
CONTROL PUSHBTN 4 ON
CONTROL PUSHBTN 5 ON
CONTROL PUSHBTN 6 ON
CONTROL PUSHBTN 7 ON
Control pushbutton 1 is being pressed
Control pushbutton 2 is being pressed
Control pushbutton 3 is being pressed
Control pushbutton 4 is being pressed
Control pushbutton 5 is being pressed
Control pushbutton 6 is being pressed
Control pushbutton 7 is being pressed
CYBERSENTRY
ROLE ADMIN ACT
ROLE SUPERVISOR ACT
ROLE ENGINEER ACT
ROLE OPERATOR ACT
ROLE OBSERVER ACT
AUTHENTICATION FAIL
UNAUTH FW ATTEMPT
UNAUTH SETTING WRITE
Administrator role is active and is set to true when that is the case
Supervisor role is active and is set to true when that is the case
Engineer role is active and is set to true when that is the case
Operator role is active and is set to true when that is the case
Observer role is active and is set to true when that is the case
Operand set for Failed Authentication self-test and alarm
Operand set for firmware lock self-test and alarm
Operand set for settings lock self-test and alarm
ELEMENT:
50DD supervision
50DD SV
50DD SV 87LG
Disturbance detector has operated
Disturbance detector for 87LG has operated
ELEMENT:
87L current
differential
87L DIFF OP
87L DIFF RECVD DTT
87L DIFF KEY DTT
87L DIFF PFLL FAIL
87L DIFF CH ASYM DET
87L DIFF CH1 FAIL
87L DIFF CH2 FAIL
87L DIFF CH1 LOSTPKT
87L DIFF CH2 LOSTPKT
87L DIFF CH1 CRCFAIL
87L DIFF CH2 CRCFAIL
87L DIFF CH1 ID FAIL
87L DIFF CH2 ID FAIL
87L DIFF GPS FAIL
87L DIFF 1 MAX ASYM
87L DIFF 2 MAX ASYM
87L DIFF 1 TIME CHNG
87L DIFF 2 TIME CHNG
87L DIFF GPS 1 FAIL
87L DIFF GPS 2 FAIL
87L DIFF BLOCKED
87L DIFF PKP G
87L DIFF OP G
At least one phase of current differential has operated
Direct transfer trip has been received
Direct transfer trip is keyed
Phase and frequency lock loop (PFLL) has failed
Channel asymmetry greater than 1.5 ms detected
Channel 1 has failed
Channel 2 has failed
Exceeded maximum lost packet threshold on channel 1
Exceeded maximum lost packet threshold on channel 2
Exceeded maximum CRC error threshold on channel 1
Exceeded maximum CRC error threshold on channel 2
The ID check for a peer L30 on channel 1 has failed
The ID check for a peer L30 on channel 2 has failed
The GPS signal failed or is not configured properly at any terminal
Asymmetry on channel 1 exceeded preset value
Asymmetry on channel 2 exceeded preset value
Change in round trip delay on channel 1 exceeded preset value
Change in round trip delay on channel 2 exceeded preset value
GPS failed at remote terminal 1 (channel 1)
GPS failed at remote terminal 1 (channel 2)
The 87L function is blocked due to communication problems
The ground differential element has picked up
The ground differential element has operated
ELEMENT:
87L in-zone
transformer
compensation
87L HARM2 A OP
87L HARM2 B OP
87L HARM2 C OP
Asserted when phase A of second harmonic of the transformer magnetizing
inrush current inhibits the current differential element from operating.
Asserted when phase B of second harmonic of the transformer magnetizing
inrush current inhibits the current differential element from operating.
Asserted when phase C of second harmonic of the transformer magnetizing
inrush current inhibits the current differential element from operating.
ELEMENT:
Autoreclose
(per CT bank)
AR1 ENABLED
AR1 RIP
AR1 LO
AR1 BLK FROM MAN CLS
AR1 CLOSE
AR1 SHOT CNT=0
AR1 SHOT CNT=1
AR1 SHOT CNT=2
AR1 SHOT CNT=3
AR1 SHOT CNT=4
AR1 DISABLED
Autoreclose 1 is enabled
Autoreclose 1 is in progress
Autoreclose 1 is locked out
Autoreclose 1 is temporarily disabled
Autoreclose 1 close command is issued
Autoreclose 1 shot count is 0
Autoreclose 1 shot count is 1
Autoreclose 1 shot count is 2
Autoreclose 1 shot count is 3
Autoreclose 1 shot count is 4
Autoreclose 1 is disabled
ELEMENT:
Auxiliary overvoltage
AUX OV1 PKP
AUX OV1 DPO
AUX OV1 OP
Auxiliary overvoltage element has picked up
Auxiliary overvoltage element has dropped out
Auxiliary overvoltage element has operated
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...