5-182
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
SYSTEM SETUP
CHAPTER 5: SETTINGS
5
PMU 1 TIMED TRIGGER POSITION
— Specifies the amount of pre-trigger data as a percent of the entire record. This setting
applies only to the timed mode of recording.
5.5.8.19 Aggregators
SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
PMU AGGREGATOR 1
PMU AGGREGATOR1 PROTOCOL
— Selects if the IEEE C37.118 or IEC 61850-90-5 technical report is used. Because one
protocol is supported at a time in a device, this setting applies to all PMU aggregators.
PMU AGGREGATOR1 IDCODE
— Numeric identifier of the Aggregator / PDC function. In an IEEE C37.118 output stream, this
identifies the ID of the aggregator, which is only used if there is more than 1 PMU mapped into an aggregator.
PMU AGGREGATOR1 PMU1
— If set to “Yes,” aggregator 1 includes the PMU1 data set in the reporting data stream.
AGGREGATOR1 does not include PMU1 data set in the report if set to “No.”
SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
PMU AGGREGATOR 1
C37.118 AGGR 1
CONFIGURATION
PMU AGGREGATOR 1 TCP PORT
— Selects the TCP port number to be used by this aggregator for network reporting. All ports,
even those of unused aggregators, must be valid and unique to avoid port number collisions.
PMU AGGREGATOR 1 UDP PORT
— Selects the UDP port number to be used by this aggregator for network reporting. All ports,
even those of unused aggregators, must be valid and unique to avoid port number collisions.
PMU AGGREGATOR 1 PDC CONTROL
— The synchrophasor standard allows for user-defined controls originating at the PDC, to
be executed on the PMU. The control is accomplished via an extended command frame. The relay decodes the first word
of the extended field, EXTFRAME, to drive 16 dedicated FlexLogic operands. Each aggregator supports 16 FlexLogic
operands, as shown in the table. The operands are asserted for five seconds following reception of the command frame. If
the new command frame arrives within the five-second period, the FlexLogic operands are updated, and the five-second
timer restarts. This setting enables or disables the control. When enabled, all 16 operands for each aggregator are active;
when disabled, all 16 operands for each aggregator remain reset.
PMU AGGREGATOR 1
PMU AGGREGATOR 1
PROTOCOL: NONE
Range: NONE, 37.118, 90-5
PMU AGGREGATOR 1
IDCODE: 1
Range: 1 to 65534 in steps of 1
PMU AGGREGATOR 1
INCLUDE PMU1: No
Range: No, Yes
C37.118 AGGR 1
CONFIGURATION
See below
90-5 AGGR 1
CONFIGURATION
See below
When the protocol selection is set via the software or keypad, all aggregators whose protocol is not set to None are
set to the last protocol saved (that is, IEEE C37.118 or IEC 61850-90-5) to any aggregators, as both IEEE C37.118 and
IEC 61850-90-5 simultaneous streaming is not possible.
Only PMUs with same reporting rate can be assigned to the same PMU AGGREGATOR.
C37.118 AGGR 1
CONFIGURATION
PMU AGGREGATOR 1
TCP PORT: 4712
Range: 0 to 65534
PMU AGGREGATOR 1:
UDP PORT: 4713
Range: 0 to 65534
PMU AGGREGATOR 1:
PDC CONTROL: Disabled
Range: Disabled, Enabled
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...