5-134
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
REMOTE RESOURCES
CHAPTER 5: SETTINGS
5
RELAY SETTINGS
— To safeguard against the installation of a relay without any entered settings, the unit does not allow
signaling of any output relay until
RELAY SETTINGS
is set to "Programmed." This setting is "Not Programmed" by default. The
UNIT NOT PROGRAMMED self-test error message displays until the relay is put into the "Programmed" state.
RELAY NAME
— This setting allows the user to uniquely identify a relay. This name appears on generated reports.
5.4 Remote resources
5.4.1 Remote resources configuration
When the L30 is ordered with a process card module as a part of HardFiber system, an additional
Remote Resources
menu tree is available in the EnerVista software to allow configuration of the HardFiber system.
Figure 5-59: Remote Resources configuration menu
The remote resources settings configure a L30 with a process bus module to work with HardFiber Bricks. Remote resources
configuration is only available through the EnerVista software, and is not available through the L30 front panel. A Brick
provides eight AC measurements, along with contact inputs, DC analog inputs, and contact outputs, to be the remote
interface to field equipment such as circuit breakers and transformers. The L30 with a process bus module has access to
all of the capabilities of up to eight Bricks. Remote resources settings configure the point-to-point connection between
specific fiber optic ports on the L30 process card and specific Brick. The relay is then configured to measure specific
currents, voltages and contact inputs from those Bricks, and to control specific outputs.
The configuration process for remote resources is straightforward and consists of the following steps.
•
Configure the field units. This establishes the point-to-point connection between a specific port on the relay process
bus module, and a specific digital core on a specific Brick. This is a necessary first step in configuring a process bus
relay.
•
Configure the AC banks. This sets the primary and secondary quantities and connections for currents and voltages. AC
bank configuration also provides a provision for redundant measurements for currents and voltages, a powerful
reliability improvement possible with process bus.
•
Configure signal sources. This functionality of the L30 has not changed other than the requirement to use currents
and voltages established by AC bank configuration under the remote resources menu.
•
Configure field contact inputs, field contact outputs, RTDs, and transducers as required for the application's
functionality. These inputs and outputs are the physical interface to circuit breakers, transformers, and other
RELAY NAME:
Relay-1
Range: up to 20 alphanumeric characters
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...