CHAPTER 5: SETTINGS
PRODUCT SETUP
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-123
5
All major self-test alarms are reported automatically with their corresponding FlexLogic operands, events, and targets.
This settings menu allows enabling and disabling of most minor self-test alarms.
When in the Disabled mode, minor alarms do not assert a FlexLogic operand, write to the event recorder, or display target
messages. Moreover, they do not trigger the ANY MINOR ALARM or ANY SELF-TEST messages. When in Enabled mode,
minor alarms continue to function along with other major and minor alarms. See the Relay Self-tests section in chapter 7
for information on major and minor self-test alarms.
When using the graphical front panel and setting annunciator alarms, the function needs to be enabled here too, else the
alarm is not triggered.
5.3.13 Control pushbuttons
SETTINGS
PRODUCT SETUP
CONTROL PUSHBUTTONS
CONTROL PUSHBUTTON 1(7)
This feature is supported with enhanced and standard front panels.
There are three standard control pushbuttons, labelled USER 1, USER 2, and USER 3, on the standard and enhanced front
panels. These are user-programmable and can be used for various applications such as performing an LED test, switching
setting groups, and invoking and scrolling though user-programmable displays.
The location of the control pushbuttons are shown in the following figures.
FIRST ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled
SEC. ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled
THIRD ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled
SFP MODULE FAIL
FUNCTION: Disabled
Range: Disabled, Enabled
BATTERY FAIL
FUNCTION: Enabled
Range: Disabled, Enabled
SNTP FAIL
FUNCTION: Enabled
Range: Disabled, Enabled
IRIG-B FAIL
FUNCTION: Enabled
Range: Disabled, Enabled
PTP FAIL
FUNCTION: Enabled
Range: Disabled, Enabled
CONTROL
PUSHBUTTON 1
CONTROL PUSHBUTTN 1 ID
CTRL PB 1
Range: up to 20 alphanumeric characters
CONTROL PUSHBUTTON 1
FUNCTION: Disabled
Range: Disabled, Enabled
CONTROL PUSHBUTTON 1
EVENTS: Disabled
Range: Disabled, Enabled
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...