CHAPTER 5: SETTINGS
PRODUCT SETUP
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-9
5
The L30 supports password entry from a local or remote connection.
Local access is defined as access to settings or commands via the front panel. This includes both keypad entry and the
RS232 port. Remote access is defined as access to settings or commands via any rear communications port. This includes
both Ethernet and RS485 connections. Any change to the local or remote password enables this functionality.
ACCESS LEVEL
— The "Restricted" option means that settings and commands can be accessed, but there is no access to
factory configuration. Access automatically reverts to the Restricted level according to the access level timeout setting
values. The access level is set to Restricted when control power is cycled.
The "Factory Service" level is not available and intended for factory use only.
There are two user security access levels, setting and command, for which you can set a password for each. Use of a
password for each level controls whether users can enter commands or change settings. Another option is to specify
setting and/or command access for individual user accounts.
•
Setting
— Allows the user to make any changes to any of the setting values:
–
Changing any setting
–
Test mode operation
•
Command
— Restricts the user from making any settings changes, but allows the user to perform the following
operations:
–
Operating the breakers via front panel keypad
–
Changing the state of virtual inputs
–
Clearing the event records
–
Clearing the oscillography records
–
Clearing fault reports
–
Changing the date and time
–
Clearing the breaker arcing current
–
Clearing the data logger
–
Clearing the user-programmable pushbutton states
When entering a settings or command password via EnerVista or any serial interface, the user must enter the
corresponding connection password. If the connection is to the back of the L30, the remote password must be used. If the
connection is to the RS232 port of the front panel, the local password must be used.
The local setting and command sessions are initiated by the user through the front panel display and are disabled either by
the user or by timeout (via the setting and command level access timeout settings). The remote setting and command
sessions are initiated by the user through the EnerVista software and are disabled either by the user or by timeout.
The state of the session (local or remote, setting or command) determines the state of the following FlexLogic operands:
•
ACCESS LOC SETG OFF
— Asserted when local setting access is disabled
•
ACCESS LOC SETG ON
— Asserted when local setting access is enabled
•
ACCESS LOC CMND OFF
— Asserted when local command access is disabled
•
ACCESS LOC CMND ON
— Asserted when local command access is enabled
•
ACCESS REM SETG OFF
— Asserted when remote setting access is disabled
•
ACCESS REM SETG ON
— Asserted when remote setting access is enabled
•
ACCESS REM CMND OFF
— Asserted when remote command access is disabled
•
ACCESS REM CMND ON
— Asserted when remote command access is enabled
DUAL PERMISSION
SECURITY ACCESS
PASSWORD ACCESS
EVENTS: Disabled
Range: Disabled, Enabled
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...