NE-M Installation Guide
H5692448
850050111
Issue 03 August 2017
30
Connect Input Power
WARNING: Shock Hazard
Disconnect all input branch circuits prior to making input connections to the system. When
connecting to any source, ensure compliance to all local and national wiring rules.
CAUTION: Equipment Damage
PV inputs must be current limited to 11A maximum.
Terminal Block are arranged to allow addition of shelves (to the bottom) and terminal blocks (from the inside out).
Shelves 1 through 7 may be rectifier shelves.
Additional converter only shelves may be added as needed – no AC power provided.
Figure 32 Input Power Terminal Block Positions
Figure 33 Rectifier / Converter and Shelf Numbering
Figure 34 Rectifier Dual Feed Jumper Positions – ac feeds only
Shelf Slot ID
Label