Non-Volatile Configuration Parameters
Parameter
Description
Default Value
IP Address
IP Address of the PNC.
0.0.0.0
Subnet Mask
Subnet mask of the PNC.
0.0.0.0
Default Gateway
Default Gateway for the PNC.
0.0.0.0
Device Name
PNC
’s PROFINET Device Name. Defaults to
empty string - indicating the PNC is not named.
””
Redundant Media
Role
Specifies whether media redundancy is disabled
or if it is enabled as a Client or if it is enabled as a
Manager.
Disabled
Redundant Media
Ring Port 1 ID
Indicates one of the two network ports involved in
Media Redundancy. Valid values are 1 to 4.
1
Redundant Media
Ring Port 2 ID
Indicates one of the two network ports involved in
Media Redundancy. Valid values are 1 to 4.
2
Redundant Media
test interval
Interval for sending test frames on ring ports in
millisecond units. Valid values are 1 to 1000.
20 ms
Redundant Media
monitor count
Indicates the number of consecutive failed test
frames before declaring a ring failure. Valid
values are 2 to 10.
3