Installation Guide
17996 Rev5, August 2013
-
The oil temperature at this location must always be below 30°C (86°F).
-
Do not use a 90° elbow to convert a vertical installation to a horizontal
installation.
-
It is recommended to set the temperature set point (
Temp SetPoint
parameter in the
Temperature
submenu) of the H201 sensor to 45°C
(113°F).
If these four recommended locations cannot be used, contact
General Electric Customer Service (contact information can be
found at the bottom of page 2) to help you determine an
acceptable alternative location.