I
NSTALLATION
REV7
/REV7
OI 250 (EN)
6.9.4
Connecting the Operating Mechanisms and Pole Columns
• Lubricate the shaft of pole B as per L2.
• Fit lever B (6) onto the shaft of pole B (2).
• Apply locking adhesive S1 to the screw (9). Secure the lever with
the screw (9) and washer (10).
Tighten to a torque of 35 Nm.
• Insert the drive rod (5) into lever B (6).
• Turn lever B (6) in the direction of the arrow until the lever and the
shaft are in contact with one another. This reduces the clearance
between the lever and the shaft.
• Pull on the drive rod to reduce the clearance between the drive
shaft and operating lever.
• Check to make sure the holes in the lever and drive rod are
aligned. If required align the pole columns using a tire lever.
“Aligning the Pole Columns Using a Tire Lever (if required)”
on Page 44)
2
Pole
1x
5
Drive rod
1x
6
Lever
1x
9
Hexagon screw, M10x25 A2-70
1x
10
Washer, 50.5/11/3
1x
11
Locking sleeve
1x
12
Washer, 6 A2
1x
13
Hexagon screw, M6x16 A2-70
1x
14
Flanged coupling pin, 16x68
1x
15
Sleeve
1x
BA
-P-2042
990-HEB
E
L
2
10
12
13
5
6
11
14
15
9
Содержание GL 311 F3/4031 P/VE
Страница 2: ......
Страница 10: ...INTRODUCTION 10 146 OI 250 EN REV7 REV6...
Страница 12: ...SAFETY 12 146 OI 250 EN REV7 REV3...
Страница 48: ...INSTALLATION 48 146 OI 250 EN REV7 REV7...
Страница 80: ...INSPECTION AND MAINTENANCE 80 146 OI 250 EN REV7 REV3...
Страница 102: ...RECONDITIONING 102 146 OI 250 EN REV7 REV7...
Страница 104: ...END OF LIFE MANAGEMENT 104 146 OI 250 EN REV7 REV2a...
Страница 114: ...SPECIAL EQUIPMENT OPTIONAL 114 146 OI 250 EN REV7 REV0...
Страница 128: ...REPLACEMENT PARTS AND ACCESSORIES 128 146 OI 250 EN REV7 REV6...
Страница 130: ...HANDLING USED SULFUR HEXAFLUORIDE 130 146 OI 250 EN REV7 REV2...