
GE Multilin
G60 Generator Protection System
8-3
8 SECURITY
8.1 PASSWORD SECURITY
8
8.1.4 REMOTE PASSWORDS
The remote password settings are only visible from a remote connection via the EnerVista UR Setup software. Select the
Settings > Product Setup > Password Security
menu item to open the remote password settings window.
Figure 8–1: REMOTE PASSWORD SETTINGS WINDOW
Proper passwords are required to enable each command or setting level access. A command or setting password consists
of 1 to 10 numerical characters and are initially programmed to “0”. The following procedure describes how the set the com-
mand or setting password.
1.
Enter the new password in the
Enter New Password
field.
2.
Re-enter the password in the
Confirm New Password
field.
3.
Click the
Change
button. This button will not be active until the new password matches the confirmation password.
4.
If the original password is not “0”, then enter the original password in the
Enter Password
field and click the
Send
Password to Device
button.
5.
The new password is accepted and a value is assigned to the
ENCRYPTED PASSWORD
item.
If a command or setting password is lost (or forgotten), consult the factory with the corresponding
Encrypted Password
value.
8.1.5 ACCESS SUPERVISION
PATH: SETTINGS
Ö
PRODUCT SETUP
Ö
SECURITY
ÖØ
ACCESS SUPERVISION
ACCESS
SUPERVISION
ACCESS LEVEL
TIMEOUTS
MESSAGE
INVALID ATTEMPTS
BEFORE LOCKOUT: 3
Range: 2 to 5 in steps of 1
MESSAGE
PASSWORD LOCKOUT
DURATION: 5 min
Range: 5 to 60 minutes in steps of 1
Содержание G60 UR Series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 102: ...3 48 G60 Generator Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 446: ...8 18 G60 Generator Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 452: ...9 6 G60 Generator Protection System GE Multilin 9 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 9 THEORY OF OPERATION 9 ...
Страница 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Страница 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Страница 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 634: ...x G60 Generator Protection System GE Multilin INDEX ...