5-256
G60 Generator Protection System
GE Multilin
5.10 TESTING
5 SETTINGS
5
The
TEST MODE FUNCTION
setting can only be changed by a direct user command. Following a restart, power up, settings
upload, or firmware upgrade, the test mode will remain at the last programmed value. This allows a G60 that has been
placed in isolated mode to remain isolated during testing and maintenance activities. On restart, the
TEST MODE FORCING
setting and the force contact input and force contact output settings all revert to their default states.
5.10.2 FORCE CONTACT INPUTS
PATH: SETTINGS
ÖØ
TESTING
ÖØ
FORCE CONTACT INPUTS
The relay digital inputs (contact inputs) could be pre-programmed to respond to the test mode in the following ways:
•
If set to “Disabled”, the input remains fully operational. It is controlled by the voltage across its input terminals and can
be turned on and off by external circuitry. This value should be selected if a given input must be operational during the
test. This includes, for example, an input initiating the test, or being a part of a user pre-programmed test sequence.
•
If set to “Open”, the input is forced to report as opened (Logic 0) for the entire duration of the test mode regardless of
the voltage across the input terminals.
•
If set to “Closed”, the input is forced to report as closed (Logic 1) for the entire duration of the test mode regardless of
the voltage across the input terminals.
The force contact inputs feature provides a method of performing checks on the function of all contact inputs. Once
enabled, the relay is placed into test mode, allowing this feature to override the normal function of contact inputs. The Test
Mode LED will be on, indicating that the relay is in test mode. The state of each contact input may be programmed as “Dis-
abled”, “Open”, or “Closed”. All contact input operations return to normal when all settings for this feature are disabled.
Table 5–27: TEST MODE OPERATION
TEST MODE
FUNCTION
TEST MODE
FORCING
OPERAND
IN-SERVICE
LED
TEST MODE
LED
CRITICAL
FAIL
RELAY
INPUT AND OUTPUT BEHAVIOR
Disabled
No effect
Unaffected
Off
Unaffected
Contact outputs and inputs are under normal
operation. Channel tests and PMU tests not
operational (where applicable).
Isolated
No effect
Off
On
De-
energized
Contact outputs are disabled and contact inputs
are operational. Channel tests and PMU tests
are also operational (where applicable).
Forcible
On (logic 1)
Off
Flashing
De-
energized
Contact inputs and outputs are controlled by the
force contact input and force contact output
functions. Channel tests and PMU tests are
operational (where applicable).
Off (logic 0)
Off
Flashing
De-
energized
Contact outputs and inputs are under normal
operation. Channel tests and PMU tests are also
operational (where applicable).
FORCE CONTACT
INPUTS
FORCE Cont Ip 1
:Disabled
Range: Disabled, Open, Closed
MESSAGE
FORCE Cont Ip 2
:Disabled
Range: Disabled, Open, Closed
↓
MESSAGE
FORCE Cont Ip xx
:Disabled
Range: Disabled, Open, Closed
Содержание G60 UR Series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 102: ...3 48 G60 Generator Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 446: ...8 18 G60 Generator Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 452: ...9 6 G60 Generator Protection System GE Multilin 9 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 9 THEORY OF OPERATION 9 ...
Страница 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Страница 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Страница 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 634: ...x G60 Generator Protection System GE Multilin INDEX ...