5-108
G60 Generator Protection System
GE Multilin
5.5 FLEXLOGIC™
5 SETTINGS
5
ELEMENT:
Split phase
protection
SPLIT PHASE A PKP
SPLIT PHASE A DPO
SPLIT PHASE A OP
SPLIT PHASE B PKP
SPLIT PHASE B DPO
SPLIT PHASE B OP
SPLIT PHASE C PKP
SPLIT PHASE C DPO
SPLIT PHASE C OP
SPLIT PHASE OP
SPLIT PHASE PKP
SPLIT PHASE DPO
Phase A of the split phase protection has picked up
Phase A of the split phase protection has dropped out
Phase A of the split phase protection has operated
Phase B of the split phase protection has picked up
Phase B of the split phase protection has dropped out
Phase B of the split phase protection has operated
Phase C of the split phase protection has picked up
Phase C of the split phase protection has dropped out
Phase C of the split phase protection has operated
The split phase protection has operated
The split phase protection has picked up
The split phase protection has dropped out
ELEMENT:
VTFF (Voltage
transformer fuse
failure)
SRC1 VT FUSE FAIL OP
SRC1 VT FUSE FAIL DPO
SRC1 VT FUSE FAIL VOL LOSS
Source 1 VT fuse failure detector has operated
Source 1 VT fuse failure detector has dropped out
Source 1 has lost voltage signals (V2 below 15% AND V1 below 5%
of nominal)
SRC2 VT FUSE FAIL to
SRC4 VT FUSE FAIL
Same set of operands as shown for SRC1 VT FUSE FAIL
ELEMENT:
Stator differential
STATOR DIFF OP
STATOR DIFF PKP A
STATOR DIFF PKP B
STATOR DIFF PKP C
STATOR DIFF OP A
STATOR DIFF OP B
STATOR DIFF OP C
STATOR DIFF DPO A
STATOR DIFF DPO B
STATOR DIFF DPO C
STATOR DIFF SAT A
STATOR DIFF SAT B
STATOR DIFF SAT C
STATOR DIFF DIR A
STATOR DIFF DIR B
STATOR DIFF DIR C
At least one phase of stator differential has operated
Phase A of stator differential has picked up
Phase B of stator differential has picked up
Phase C of stator differential has picked up
Phase A of stator differential has operated
Phase B of stator differential has operated
Phase C of stator differential has operated
Phase A of stator differential has dropped out
Phase B of stator differential has dropped out
Phase C of stator differential has dropped out
Phase A of stator differential has is saturated
Phase B of stator differential has is saturated
Phase C of stator differential has is saturated
Phase A of stator differential phase comparison has been satisfied
Phase B of stator differential phase comparison has been satisfied
Phase C of stator differential phase comparison has been satisfied
ELEMENT:
Disconnect switch
SWITCH 1 OFF CMD
SWITCH 1 ON CMD
SWITCH 1
Φ
A BAD ST
SWITCH 1
Φ
A INTERM
SWITCH 1
Φ
A CLSD
SWITCH 1
Φ
A OPEN
SWITCH 1
Φ
B BAD ST
SWITCH 1
Φ
A INTERM
SWITCH 1
Φ
B CLSD
SWITCH 1
Φ
B OPEN
SWITCH 1
Φ
C BAD ST
SWITCH 1
Φ
A INTERM
SWITCH 1
Φ
C CLSD
SWITCH 1
Φ
C OPEN
SWITCH 1 BAD STATUS
SWITCH 1 CLOSED
SWITCH 1 OPEN
SWITCH 1 DISCREP
SWITCH 1 TROUBLE
Disconnect switch 1 open command initiated
Disconnect switch 1 close command initiated
Disconnect switch 1 phase A bad status is detected (discrepancy between
the 52/a and 52/b contacts)
Disconnect switch 1 phase A intermediate status is detected (transition from
one position to another)
Disconnect switch 1 phase A is closed
Disconnect switch 1 phase A is open
Disconnect switch 1 phase B bad status is detected (discrepancy between
the 52/a and 52/b contacts)
Disconnect switch 1 phase A intermediate status is detected (transition from
one position to another)
Disconnect switch 1 phase B is closed
Disconnect switch 1 phase B is open
Disconnect switch 1 phase C bad status is detected (discrepancy between
the 52/a and 52/b contacts)
Disconnect switch 1 phase A intermediate status is detected (transition from
one position to another)
Disconnect switch 1 phase C is closed
Disconnect switch 1 phase C is open
Disconnect switch 1 bad status is detected on any pole
Disconnect switch 1 is closed
Disconnect switch 1 is open
Disconnect switch 1 has discrepancy
Disconnect switch 1 trouble alarm
SWITCH 2...
Same set of operands as shown for SWITCH 1
ELEMENT:
Synchrocheck
SYNC 1 DEAD S OP
SYNC 1 DEAD S DPO
SYNC 1 SYNC OP
SYNC 1 SYNC DPO
SYNC 1 CLS OP
SYNC 1 CLS DPO
SYNC 1 V1 ABOVE MIN
SYNC 1 V1 BELOW MAX
SYNC 1 V2 ABOVE MIN
SYNC 1 V2 BELOW MAX
Synchrocheck 1 dead source has operated
Synchrocheck 1 dead source has dropped out
Synchrocheck 1 in synchronization has operated
Synchrocheck 1 in synchronization has dropped out
Synchrocheck 1 close has operated
Synchrocheck 1 close has dropped out
Synchrocheck 1 V1 is above the minimum live voltage
Synchrocheck 1 V1 is below the maximum dead voltage
Synchrocheck 1 V2 is above the minimum live voltage
Synchrocheck 1 V2 is below the maximum dead voltage
SYNC 2
Same set of operands as shown for SYNC 1
Table 5–9: G60 FLEXLOGIC™ OPERANDS (Sheet 6 of 9)
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
Содержание G60 UR Series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 102: ...3 48 G60 Generator Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 446: ...8 18 G60 Generator Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 452: ...9 6 G60 Generator Protection System GE Multilin 9 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 9 THEORY OF OPERATION 9 ...
Страница 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Страница 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Страница 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 634: ...x G60 Generator Protection System GE Multilin INDEX ...