B-44
G30 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
7633
...Repeated for Disconnect Switch 14
7652
...Repeated for Disconnect Switch 15
Thermal Overload Protection (Read/Write Settings) (2 modules)
7788
Thermal Protection 1 Function
0 to 1
---
1
F102
0 (Disabled)
7789
Thermal Protection 1 Source
0 to 5
---
1
F167
0 (SRC 1)
778A
Thermal Protection 1 Base Current
0.2 to 3
pu
0.01
F001
80
778B
Thermal Protection 1 K Factor
1 to 1.2
---
0.05
F001
110
778C
Thermal Protection 1 Trip Time Constant
0 to 1000
min.
1
F001
45
778D
Thermal Protection 1 Reset Time Constant
0 to 1000
min.
1
F001
45
778E
Thermal Protection 1 Minimum Reset Time
0 to 1000
min.
1
F001
20
778F
Thermal Protection 1 Reset
0 to 4294967295
---
1
F300
0
7791
Thermal Protection 1 Block
0 to 4294967295
---
1
F300
0
7793
Thermal Protection 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7794
Thermal Protection 1 Events
0 to 1
---
1
F102
0 (Disabled)
7795
Reserved (2 items)
---
---
---
F001
0
7797
Repeated for Thermal Protection 2
Ohm Inputs (Read/Write Setting) (2 modules)
77F8
Ohm Inputs 1 Function
0 to 1
---
1
F102
0 (Disabled)
77F9
Ohm Inputs 1 ID
---
---
---
F205
"Ohm Ip 1 "
77FF
Ohm Inputs 1 Reserved (9 items)
0 to 65535
---
1
F001
0
7808
...Repeated for Ohm Inputs 2
Underfrequency (Read/Write Setting) (6 modules)
7A80
Underfrequency 1 Function
0 to 1
---
1
F102
0 (Disabled)
7A81
Underfrequency 1 Block
0 to 4294967295
---
1
F300
0
7A83
Underfrequency 1 Min Current
0.1 to 1.25
pu
0.01
F001
10
7A84
Underfrequency 1 Pickup
20 to 65
Hz
0.01
F001
5950
7A85
Underfrequency 1 Pickup Delay
0 to 65.535
s
0.001
F001
2000
7A86
Underfrequency 1 Reset Delay
0 to 65.535
s
0.001
F001
2000
7A87
Underfrequency 1 Source
0 to 5
---
1
F167
0 (SRC 1)
7A88
Underfrequency 1 Events
0 to 1
---
1
F102
0 (Disabled)
7A89
Underfrequency 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7A8A
Underfrequency 1 Reserved (5 items)
0 to 1
---
1
F001
0
7A8F
...Repeated for Underfrequency 2
7A9E
...Repeated for Underfrequency 3
7AAD
...Repeated for Underfrequency 4
7ABC
...Repeated for Underfrequency 5
7ACB
...Repeated for Underfrequency 6
User Programmable Pushbuttons (Read/Write Setting) (16 modules)
7B60
User Programmable Pushbutton 1 Function
0 to 2
---
1
F137
0 (Disabled)
7B61
User Programmable Pushbutton 1 Top Line
---
---
---
F202
(none)
7B6B
User Programmable Pushbutton 1 On Text
---
---
---
F202
(none)
7B75
User Programmable Pushbutton 1 Off Text
---
---
---
F202
(none)
7B7F
User Programmable Pushbutton 1 Drop-Out Time
0 to 60
s
0.05
F001
0
7B80
User Programmable Pushbutton 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7B81
User Programmable Pushbutton 1 Events
0 to 1
---
1
F102
0 (Disabled)
7B82
User Programmable Pushbutton 1 LED Operand
0 to 4294967295
---
1
F300
0
7B84
User Programmable Pushbutton 1 Autoreset Delay
0.2 to 600
s
0.1
F001
10
7B85
User Programmable Pushbutton 1 Autoreset Function
0 to 1
---
1
F102
0 (Disabled)
7B86
User Programmable Pushbutton 1 Local Lock Operand
0 to 4294967295
---
1
F300
0
7B88
User Programmable Pushbutton 1 Message Priority
0 to 2
---
1
F220
0 (Disabled)
7B89
User Programmable Pushbutton 1 Remote Lock Operand
0 to 4294967295
---
1
F300
0
7B8B
User Programmable Pushbutton 1 Reset Operand
0 to 4294967295
---
1
F300
0
7B8D
User Programmable Pushbutton 1 Set Operand
0 to 4294967295
---
1
F300
0
7B8F
User Programmable Pushbutton 1 Hold
0 to 10
s
0.1
F001
1
Table B–10: MODBUS MEMORY MAP (Sheet 36 of 64)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...