GE Multilin
G30 Generator Protection System
B-39
APPENDIX B
B.4 MEMORY MAPPING
B
5F4A
Frequency Out-Of-Band Accumulator Lower Frequency
Array (7 items)
20 to 70
Hz
0.01
F001
6000
5F51
Frequency Out-Of-Band Accumulator Min Value V A
0.1 to 1.25
pu
0.01
F001
10
5F52
Frequency Out-Of-Band Accumulator Source
0 to 5
---
1
F167
0 (SRC 1)
5F53
Frequency Out-Of-Band Accumulator Target Messages
Enable
0 to 2
---
1
F109
0 (Self-reset)
5F54
Frequency Out-Of-Band Accumulator Time Limit Array (7
items)
1 to 65535
sec
1
F001
200
5F5B
Frequency Out-Of-Band Accumulator Time Preset Array (7
items)
0 to 65535
sec
1
F001
0
5F62
Frequency Out-Of-Band Accumulator Upper Frequency
Array (7 items)
20 to 70
Hz
0.01
F001
6000
Setting Groups (Read/Write Setting)
5F70
Setting Group for Modbus Comms (0 means group 1)
0 to 5
---
1
F001
0
5F71
Setting Groups Block
0 to 4294967295
---
1
F300
0
5F73
FlexLogic Operands to Activate Groups 2 through 6 (5
items)
0 to 4294967295
---
1
F300
0
5F7D
Setting Group Function
0 to 1
---
1
F102
0 (Disabled)
5F7E
Setting Group Events
0 to 1
---
1
F102
0 (Disabled)
Setting Groups (Read Only)
5F7F
Current Setting Group
0 to 5
---
1
F001
0
Setting Group Names (Read/Write Setting)
5F8C
Setting Group 1 Name
---
---
---
F203
(none)
5F94
Setting Group 2 Name
---
---
---
F203
(none)
5F9C
Setting Group 3 Name
---
---
---
F203
(none)
5FA4
Setting Group 4 Name
---
---
---
F203
(none)
5FAC
Setting Group 5 Name
---
---
---
F203
(none)
5FB4
Setting Group 6 Name
---
---
---
F203
(none)
Transformer Percent Differential (Read/Write Grouped Setting)
61C0
Percent Differential Function
0 to 1
---
1
F102
0 (Disabled)
61C1
Percent Differential Pickup
0.05 to 1
pu
0.001
F001
100
61C2
Percent Differential Slope 1
15 to 100
%
1
F001
25
61C3
Percent Differential Break 1
1 to 2
pu
0.001
F001
2000
61C4
Percent Differential Break 2
2 to 30
pu
0.001
F001
8000
61C5
Percent Differential Slope 2
50 to 100
%
1
F001
100
61C6
Inrush Inhibit Function
0 to 2
---
1
F168
1 (Adapt. 2nd)
61C7
Inrush Inhibit Level
1 to 40
%fo
0.1
F001
200
61C8
Overexcitation Inhibit Function
0 to 1
---
1
F169
0 (Disabled)
61C9
Overexcitation Inhibit Level
1 to 40
%fo
0.1
F001
100
61CA
Percent Differential Block
0 to 4294967295
---
1
F300
0
61CC
Percent Differential Target
0 to 2
---
1
F109
0 (Self-reset)
61CD
Percent Differential Events
0 to 1
---
1
F102
0 (Disabled)
61CE
Transformer Inrush Inhibit Mode
0 to 2
---
1
F189
0 (Per phase)
Negative Sequence Overvoltage (Read/Write Grouped Setting) (3 modules)
6440
Negative Sequence Overvoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
6441
Negative Sequence Overvoltage 1 Source
0 to 5
---
1
F167
0 (SRC 1)
6442
Negative Sequence Overvoltage 1 Pickup
0 to 1.25
pu
0.001
F001
300
6443
Negative Sequence Overvoltage 1 Pickup Delay
0 to 600
s
0.01
F001
50
6444
Negative Sequence Overvoltage 1 Reset Delay
0 to 600
s
0.01
F001
50
6445
Negative Sequence Overvoltage 1 Block
0 to 4294967295
---
1
F300
0
6447
Negative Sequence Overvoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
6448
Negative Sequence Overvoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
6449
...Repeated for Negative Sequence Overvoltage 2
6452
...Repeated for Negative Sequence Overvoltage 3
Overfrequency (Read/Write Setting) (4 modules)
6470
Overfrequency 1 Function
0 to 1
---
1
F102
0 (Disabled)
Table B–10: MODBUS MEMORY MAP (Sheet 31 of 64)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...