GE Multilin
G30 Generator Protection System
9-7
9 APPLICATION OF SETTINGS
9.1 SETTING EXAMPLE
9
The minimum operate time of stage 1 will be set to 0.25 seconds, the maximum operating time will be 10 minutes, and the
reset time will be set to 4 minutes.
Stage 2 is typically set lower than stage 1 with a time delay to prevent nuisance alarms for external faults that are normally
cleared by system protection. For the application example, the pickup setting is:
(EQ 9.6)
Source 2 will be chosen for this element. The settings are as follows:
9.1.6 LOSS OF EXCITATION
For the example system, we have the following values:
(EQ 9.7)
(EQ 9.8)
(EQ 9.9)
(EQ 9.10)
(EQ 9.11)
(EQ 9.12)
(EQ 9.13)
(EQ 9.14)
The voltage supervision setting will be determined by a system study and may be disabled on either element if required. VT
fuse failure should supervise this element.
Pickup
70%
I
2
capability
×
0.70 8%
×
5.6%
=
=
=
Z
b
sec
(
)
base kV
2
base MVA
---------------------------
CT ratio
VT ratio
---------------------
×
18 kV
(
)
2
211.765 MVA
------------------------------------
1600
157.5
---------------
×
15.54
Ω
=
=
=
X
d
′
(sec)
X
d
′
Z
b
(sec)
×
0.216 15.54
Ω
×
3.36
Ω
=
=
=
X
d
sec
(
)
X
d
Z
b
sec
(
)
×
1.967 15.54
Ω
×
30.57
Ω
=
=
=
CENTER 1
Z
b
sec
(
)
X
d
′
(sec)
+
2
-------------------------------------------------
15.54
Ω
3.36
Ω
+
2
-------------------------------------------
9.45
Ω
=
=
=
RADIUS 1
Z
b
sec
(
)
2
--------------------
15.54
Ω
2
----------------------
7.77
Ω
=
=
=
PICKUP DELAY 1
0.06 seconds
=
CENTER 2
X
d
sec
(
)
X
d
′
(sec)
+
2
-------------------------------------------------
30.57
Ω
3.36
Ω
+
2
-------------------------------------------
16.97
Ω
=
=
=
RADIUS 2
X
d
sec
(
)
2
---------------------
30.57
Ω
2
----------------------
15.28
Ω
=
=
=
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...