9 APPLICATION OF SETTINGS
9.1 SETTING EXAMPLE
9
The G30 requires the use of the transformer windings settings for the differential element, even if the differential is applied
only as a stator differential for the generator. These settings ensure that the differential element operates with the correct
phase shifts, and applies the correct magnitude compensation. Loss of excitation and reverse power can be assigned to
either source. Since there is no transformer involved, the phase shift to enter is the –180° phase shift due to the CT polari-
ties and connections.
9.1.2 SYSTEM SETUP
Ideally, the CTs should be selected so the generator nominal current is 80 to 85% of CT primary. The following settings are
entered for the example system. The M5 bank and the ground CT input on each of the groups are unused in this example.
The nominal current is given by:
(EQ 9.1)
Make the following settings changes in EnerVista UR Setup (or alternately, via the front panel through the
SYSTEM SETUP
AC INPUTS
CURRENT BANK F1
and the
SYSTEM SETUP
AC INPUTS
CURRENT BANK M1
menus).
For the example system, the voltage settings are calculated as follows:
PHASE VT SECONDARY =
(EQ 9.2)
PHASE VT RATIO =
(EQ 9.3)
NEUTRAL VT RATIO =
(EQ 9.4)
I
nom
13.8 kV
(
)
S
nom
3
V
nom
---------------------
162 10
6
×
VA
3 13.8 10
3
×
×
V
-----------------------------------------------
6800 A
=
=
=
18000 V
3
----------------------
120 V
13800 V
----------------------
×
69 V
=
13800 V
120 V
----------------------
115
=
13800 V
3 240 V
×
-----------------------------
33
=
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...