5-178
G30 Generator Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
Figure 5–68: GROUND IOC1 SCHEME LOGIC
d) RESTRICTED GROUND FAULT
(ANSI 87RGF, IEC PNDF)
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
GROUND CURRENT
RESTRICTED GROUND FAULT 1(4)
Restricted ground fault (RGF) protection provides sensitive ground fault detection for low-magnitude fault currents, primar-
ily faults close to the neutral point of a wye-connected winding. An internal ground fault on an impedance grounded wye
winding will produce a fault current dependent on the ground impedance value and the fault position on the winding with
respect to the neutral point. The resultant primary current will be negligible for faults on the lower 30% of the winding since
the fault voltage is not the system voltage, but rather the result of the transformation ratio between the primary windings
and the percentage of shorted turns on the secondary. Therefore, the resultant differential currents may be below the slope
threshold of the main differential element and the fault could go undetected. Application of the restricted ground fault pro-
tection extends the coverage towards the neutral point (see the
RGF and Percent Differential Zones of Protection
diagram).
RESTRICTED GROUND
FAULT 1
RESTD GND FT1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
RESTD GND FT1
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
RESTD GND FT1
PICKUP: 0.080
pu
Range: 0.005 to 30.000 pu in steps of 0.001
MESSAGE
RESTD GND FT1
SLOPE: 40%
Range: 0 to 100% in steps of 1
MESSAGE
RESTD GND FT1 PICKUP
DELAY: 0.10
s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
RESTD GND FT1 RESET
DELAY: 0.00 s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
RESTD GND FT1 BLOCK:
Off
Range: FlexLogic operand
MESSAGE
RESTD GND FT1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
RESTD GND FT1
EVENTS: Disabled
Range: Disabled, Enabled
SETTING
GROUND IOC1
FUNCTION:
Enabled = 1
SETTING
GROUND IOC1
SOURCE:
IG
GROUND IOC1
BLOCK:
Off = 0
FLEXLOGIC OPERANDS
GROUND IOIC DPO
GROUND IOC1 OP
SETTING
SETTING
IG
PICKUP
GROUND IOC1
PICKUP:
RUN
GROUND IOC1 PICKUP
DELAY:
SETTINGS
GROUND IOC1 RESET
DELAY:
t
PKP
t
RST
827037A5.VSD
AND
GROUND IOC1 PKP
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...