Troubleshooting AutoTuning
Troubleshooting
Troubleshooting AutoTuning
Table 58
Troubleshooting AutoTuning
Problem
Presumed Cause
Remedy
See Section
Auto tuning requests are
rejected.
Either or both of the A/O block
and transducer block are not in
O/S mode.
Change the target modes
of the AO and transducer
block to O/S.
“Function Block
Parameters” on
page 183
When auto tuning has
finished,
AUTO_TUNE_RESULT
changes value to an index
from 21 to 23.
There is something wrong with
the air supply pressure or
spring range.
Check whether the
measured pressure
reading nearly equals the
actual pressure. See the
descriptions for auto
tuning.
❑
“Carrying out
Tuning” on
page 61
❑
When auto tuning has
finished,
AUTO_TUNE_RESULT
changes value to index 40
or 120.
There is something wrong with
the operation point of the I/P
module.
SERVO_OFFSET could not
be measured.
If there is nothing wrong
with the air supply
pressure and piping,
contact the nearest
service station or
representative office.
—
When auto tuning has
finished,
AUTO_TUNE_RESULT
changes value to an index
from 42 to 44, or from 120
to 123.
The measured time delay
constant, hysteresis, and/or
slip width of the valve is
excessively large.
Check whether they meet
the characteristics
specified for the valve.
See the descriptions for
auto tuning.
❑
“Carrying out
Tuning” on
page 61
❑
When auto tuning has
finished,
AUTO_TUNE_RESULT
changes value to an index
from 60 to 62, or from 100
to 103.
The span of rotation angle is
incorrect or the 50% position
deviation from the horizontal
level is too large.
Correct the installation and
try auto tuning again.
❑
“Installing the
FVP110 on the
Actuator” on
page 35
❑
“Carrying out
Tuning” on
page 61
When auto tuning has
finished,
AUTO_TUNE_RESULT
changes value to an index
from 60 to 62, or from 120
to 123.
The valve hysteresis is large.
Carry out manual tuning.
Содержание FVP110
Страница 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Страница 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Страница 98: ...FVP 110 Fieldbus Valve Positioner Manual 82 GE Energy Figure 47 Double Acting Actuator Dimensions ...
Страница 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Страница 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 114: ...FVP 110 Fieldbus Valve Positioner Manual 98 GE Energy Table 17 View Object for Transducer Block ...
Страница 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Страница 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Страница 118: ...FVP 110 Fieldbus Valve Positioner Manual 102 GE Energy Table 19 View Object for DI1 DI2 Function Block ...
Страница 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Страница 120: ...FVP 110 Fieldbus Valve Positioner Manual 104 GE Energy Table 21 View Object for PID Function Block ...
Страница 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Страница 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Страница 239: ...223 LM Parameter List Link Master Functions ...
Страница 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Страница 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Страница 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Страница 268: ...FVP 110 Fieldbus Valve Positioner Manual 252 GE Energy Figure 84 Checking Position at Which Clamp Should Be Fixed ...
Страница 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 289: ...273 H Customer Maintenance Parts List ...
Страница 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Страница 291: ......