131
Fail-safe Action
Transducer Block
Fail-safe Action
If the
A/D converter failure
,
position sensor failure
, or
deviation error
event occurs in the
XD_ERROR, the transducer block activates the specified fail-safe action by cutting the
current signal to the I/P module to zero. In addition, in the event of
position sensor
failure
or
deviation error
, the fail-safe action is not deactivated even when the cause of
the failure/error is cleared. Writing
Clear non-latch
to the parameter
RELEASE_FAILSAFE deactivates the fail-safe action. The fail-safe action activated in
the event of
A/D converter failure
is deactivated automatically when the cause of the
failure is cleared.
Operation Result Integration
The FVP110 has a function to integrate the following operation result quantities
individually. To reset an integrated quantity, write
0
to the corresponding parameter.
TOTAL_CYCLE_
COUNT
Incremented by 1 at each change in the direction of the valve
action, indicating the total number of times of changes in direc-
tion of valve actions.
TOTAL_TRAVEL
Total travel distance of the stem position, shown as a percent-
age of the valve position span.
TOTAL_OPEN_TIME
and TOTAL_CLOSE_
TIME
TOTAL_CLOSE_TIME contains the integrated time periods (in
hours) when the valve position is equal to or less than the
thresholds previously set in OPEN_CLOSE_THRESHOLD.
TOTAL_OPEN_TIME is the integrated time periods (in hours)
other than TOTAL_CLOSE_TIME.
TOTAL_NEAR_
CLOSE_TIM
Total time period (in hours) when the valve position is within the
threshold set in NEAR_CLOSE_THRESHOLD.
SERVO_WARN_
COUNT
Total number of times the servo output drift warning occurred.
Indicates the total number of times a drift warning occurred
regarding the output current to the I/P module.
Recording of Revisions
When you make a change to the setting of a static parameter, the change is counted-up
in the parameter ST_REV and an update event is generated.
Содержание FVP110
Страница 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Страница 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Страница 98: ...FVP 110 Fieldbus Valve Positioner Manual 82 GE Energy Figure 47 Double Acting Actuator Dimensions ...
Страница 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Страница 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 114: ...FVP 110 Fieldbus Valve Positioner Manual 98 GE Energy Table 17 View Object for Transducer Block ...
Страница 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Страница 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Страница 118: ...FVP 110 Fieldbus Valve Positioner Manual 102 GE Energy Table 19 View Object for DI1 DI2 Function Block ...
Страница 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Страница 120: ...FVP 110 Fieldbus Valve Positioner Manual 104 GE Energy Table 21 View Object for PID Function Block ...
Страница 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Страница 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Страница 239: ...223 LM Parameter List Link Master Functions ...
Страница 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Страница 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Страница 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Страница 268: ...FVP 110 Fieldbus Valve Positioner Manual 252 GE Energy Figure 84 Checking Position at Which Clamp Should Be Fixed ...
Страница 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 289: ...273 H Customer Maintenance Parts List ...
Страница 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Страница 291: ......