129
Travel Calibration
Transducer Block
Travel Calibration
WARNING
This function strokes the valve over its full range. Do not
execute while valve is controlling the process. Keep away
from the movable parts to avoid injury.
To calibrate the travel of the valve stem, i.e., the stroke of the valve:
1. Set the valve stem to the desired position by changing the value of
FINAL_VALUE.value.
2. Set the AO block and the transducer block to O/S mode.
3. Write the value from the following choices:
❑
1 = off
❑
2 = 0% point calibration. Calibrates only the 0% point and shifts the 100% point
by the delta in the 0% point, while leaving the span unchanged.
❑
3 = span calibration. Calibrates only the 100% point while leaving the 0% point
unchanged.
❑
4 = 50% point calibration. Calibrates at the 50% point while leaving the 0% point
and 100% point unchanged.
The 50%-point calibration (in other words, linearity calibration) is intended to minimize
the linearity error at the 50% point. Also, if the feedback lever slightly deviates from a
horizontal level due to careless FVP110 positioner installation, an error caused by this
shift is corrected by the 50%-point calibration. Carrying out auto tuning of Index 2 or 4
clears the 50% calibration result. Carry out the 50%-point calibration after other tuning
has finished.
The result of Travel calibration, which is written to TRAVEL_ CALIB_RESULT as shown
in Table 35 on page 127, may be an error or warning. An error invalidates the tuning
and does not update the parameter settings.
Online Diagnostics
The FVP110 features functions to diagnose the FVP110 itself and valve actions while
online. The following describes the self-diagnostics function related to the transducer
block.
XD_ERROR
The transducer block performs self-diagnostics and writes the results to the parameter
XD_ERROR. Table 36 shows the meanings of these results in XD_ERROR.
When the content of XD_ERROR or BLOCK_ERR becomes a nonzero value, an alarm
is output to the parameter BLOCK_ALM.
Содержание FVP110
Страница 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Страница 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Страница 98: ...FVP 110 Fieldbus Valve Positioner Manual 82 GE Energy Figure 47 Double Acting Actuator Dimensions ...
Страница 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Страница 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 114: ...FVP 110 Fieldbus Valve Positioner Manual 98 GE Energy Table 17 View Object for Transducer Block ...
Страница 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Страница 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Страница 118: ...FVP 110 Fieldbus Valve Positioner Manual 102 GE Energy Table 19 View Object for DI1 DI2 Function Block ...
Страница 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Страница 120: ...FVP 110 Fieldbus Valve Positioner Manual 104 GE Energy Table 21 View Object for PID Function Block ...
Страница 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Страница 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Страница 239: ...223 LM Parameter List Link Master Functions ...
Страница 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Страница 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Страница 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Страница 268: ...FVP 110 Fieldbus Valve Positioner Manual 252 GE Energy Figure 84 Checking Position at Which Clamp Should Be Fixed ...
Страница 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Страница 289: ...273 H Customer Maintenance Parts List ...
Страница 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Страница 291: ......