5
5.3.4 BREAKERS
PATH: SETTINGS
ÖØ
SYSTEM SETUP
ÖØ
BREAKERS
Ö
BREAKER 1(2)
BREAKER 1
BREAKER 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
BREAKER1 PUSH BUTTON
CONTROL: Disabled
Range: Disabled, Enabled
MESSAGE
BREAKER 1 NAME:
Bkr 1
Range: up to 6 alphanumeric characters
MESSAGE
BREAKER 1 MODE:
3-Pole
Range: 3-Pole, 1-Pole
MESSAGE
BREAKER 1 OPEN:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1 BLK OPEN:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1 CLOSE:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1 BLK CLOSE:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1
Φ
A/3P CLSD:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1
Φ
A/3P OPND:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1
Φ
B CLOSED:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1
Φ
B OPENED:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1
Φ
C CLOSED:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1
Φ
C OPENED:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1 Toperate:
0.070 s
Range: 0.000 to 2.000 s in steps of 0.001
MESSAGE
BREAKER 1 EXT ALARM:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1 ALARM
DELAY: 0.000
s
Range: 0.000 to 1 000 000.000 s in steps of 0.001
MESSAGE
MANUAL CLOSE RECAL1
TIME: 0.000
s
Range: 0.000 to 1 000 000.000 s in steps of 0.001
MESSAGE
BREAKER 1 OUT OF SV:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1 EVENTS:
Disabled
Range: Disabled, Enabled
Содержание F60 UR Series
Страница 2: ......
Страница 4: ......
Страница 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 96: ...3 48 F60 Feeder Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Страница 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Страница 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Страница 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 558: ...x F60 Feeder Protection System GE Multilin INDEX ...