D60 Line Distance Protection System
GE Multilin
5.10 TESTING
5 SETTINGS
5
5.10.4 PHASOR MEASUREMENT UNIT TEST VALUES
PATH: SETTINGS
TESTING
PMU TEST VALUES
PMU 1 TEST VALUES
The relay must be in test mode to use the PMU test mode. That is, the
TESTING
TEST MODE FUNCTION
setting must be
“Enabled” and the
TESTING
TEST MODE INITIATE
initiating signal must be “On”.
PMU 1
TEST VALUES
PMU 1 TEST
FUNCTION: Disabled
Range: Enabled, Disabled
MESSAGE
PMU 1 VA TEST
MAGNITUDE: 500.00 kV
Range: 0.00 to 700.00 kV in steps of 0.01
MESSAGE
PMU 1 VA TEST
ANGLE: 0.00°
Range: –180.00 to 180.00° in steps of 0.05
MESSAGE
PMU 1 VB TEST
MAGNITUDE: 500.00 kV
Range: 0.00 to 700.00 kV in steps of 0.01
MESSAGE
PMU 1 VB TEST
ANGLE: –120.00°
Range: –180.00 to 180.00° in steps of 0.05
MESSAGE
PMU 1 VC TEST
MAGNITUDE: 500.00 kV
Range: 0.00 to 700.00 kV in steps of 0.01
MESSAGE
PMU 1 VC TEST
ANGLE: 120.00°
Range: –180.00 to 180.00° in steps of 0.05
MESSAGE
PMU 1 VX TEST
MAGNITUDE: 500.00 kV
Range: 0.00 to 700.00 kV in steps of 0.01
MESSAGE
PMU 1 VX TEST
ANGLE: 0.00°
Range: –180.00 to 180.00° in steps of 0.05
MESSAGE
PMU 1 IA TEST
MAGNITUDE: 1.000 kA
Range: 0.000 to 9.999 kA in steps of 0.001
MESSAGE
PMU 1 IA TEST
ANGLE: –10.00°
Range: –180.00 to 180.00° in steps of 0.05
MESSAGE
PMU 1 IB TEST
MAGNITUDE: 1.000 kA
Range: 0.000 to 9.999 kA in steps of 0.001
MESSAGE
PMU 1 IB TEST
ANGLE: –130.00°
Range: –180.00 to 180.00° in steps of 0.05
MESSAGE
PMU 1 IC TEST
MAGNITUDE: 1.000 kA
Range: 0.000 to 9.999 kA in steps of 0.001
MESSAGE
PMU 1 IC TEST
ANGLE: 110.00°
Range: –180.00 to 180.00° in steps of 0.05
MESSAGE
PMU 1 IG TEST
MAGNITUDE: 0.000 kA
Range: 0.000 to 9.999 kA in steps of 0.001
MESSAGE
PMU 1 IG TEST
ANGLE: 0.00°
Range: –180.00 to 180.00° in steps of 0.05
MESSAGE
PMU 1 TEST
FREQUENCY: 60.000 Hz
Range: 20.000 to 60.000 Hz in steps of 0.001
MESSAGE
PMU 1 TEST
df/dt: 0.000 Hz/s
Range: –10.000 to 10.000 Hz/s in steps of 0.001
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...