GE Multilin
D60 Line Distance Protection System
5-341
5 SETTINGS
5.7 CONTROL ELEMENTS
5
BLK1 FORCE TX STOP1-2
: This setting defines the FlexLogic operand of a protection element that is used for identifying inter-
nal faults on the protected line, and thus, for stopping the blocking signal. Typically forward-looking under-reach distance
elements are used as
BLK1 FORCE TX STOP
.
i) DIRECTIONAL COMPARISON UNBLOCKING
PATH: SETTINGS
CONTROL ELEMENTS
PILOT SCHEMES
DCUB SCHEME
DCUB SCHEME
DCUB SCHEME
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
DCUB BLOCK:
Off
Range: FlexLogic operand
MESSAGE
DCUB PERMISSIVE
ECHO: Disabled
Range: Disabled, Enabled, Custom
MESSAGE
DCUB ECHO COND:
Off
Range: FlexLogic operand
MESSAGE
GND DIR O/C FWD:
Off
Range: FlexLogic operand
MESSAGE
GND DIR O/C REV:
Off
Range: FlexLogic operand
MESSAGE
TRANS BLOCK PICKUP
DELAY: 0.020 s
Range: 0 to 65.535 s in steps of 0.001
MESSAGE
TRANS BLOCK RESET
DELAY: 0.090 s
Range: 0 to 65.535 s in steps of 0.001
MESSAGE
ECHO DURATION:
0.100 s
Range: 0 to 65.535 s in steps of 0.001
MESSAGE
ECHO LOCKOUT:
0.250 s
Range: 0 to 65.535 s in steps of 0.001
MESSAGE
LINE END OPEN PICKUP
DELAY: 0.050 s
Range: 0 to 65.535 s in steps of 0.001
MESSAGE
DCUB LOG PICKUP
DELAY: 0.008 s
Range: 0 to 65.535 s in steps of 0.001
MESSAGE
GUARD HEALTHY RESET
DELAY: 0.015 s
Range: 0 to 65.535 s in steps of 0.001
MESSAGE
DCUB LOG TRIP
WINDOW: 0.150 s
Range: 0 to 65.535 s in steps of 0.001
MESSAGE
DCUB SEAL-IN
DELAY: 0.010 s
Range: 0 to 65.535 s in steps of 0.001
MESSAGE
DCUB NO OF COMM
BITS: 1
Range: 1, 2, or 4
MESSAGE
DCUB RX1:
Off
Range: FlexLogic operand
MESSAGE
DCUB LOG1:
Off
Range: FlexLogic operand
MESSAGE
DCUB RX2:
Off
Range: FlexLogic operand
MESSAGE
DCUB LOG2:
Off
Range: FlexLogic operand
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...