5-176
D60 Line Distance Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
Figure 5–73: QUADRILATERAL DISTANCE CHARACTERISTIC SAMPLE SHAPES
•
PHS DIST Z1 XFMR VOL CONNECTION:
The phase distance elements can be applied to look through a three-phase
delta-wye or wye-delta power transformer. In addition, VTs and CTs could be located independently from one another
at different windings of the transformer. If the potential source is located at the correct side of the transformer, this set-
ting shall be set to “None”.
This setting specifies the location of the voltage source with respect to the involved power transformer in the direction
of the zone. The following figure illustrates the usage of this setting. In section (a), zone 1 is looking through a trans-
former from the delta into the wye winding. Therefore, the Z1 setting shall be set to “Dy11”. In section (b), Zone 4 is
looking through a transformer from the wye into the delta winding. Therefore, the Z4 setting shall be set to “Yd1”. The
zone is restricted by the potential point (location of the VTs) as illustrated in Figure (e).
•
PHS DIST Z1 XFMR CUR CONNECTION:
This setting specifies the location of the current source with respect to the
involved power transformer in the direction of the zone. In section (a) of the following figure, zone 1 is looking through
a transformer from the delta into the wye winding. Therefore, the Z1 setting shall be set to “Dy11”. In section (b), the
CTs are located at the same side as the read point. Therefore, the Z4 setting shall be set to “None”.
See the
Theory of operation
chapter for more details, and the
Application of settings
chapter for information on calcu-
lating distance reach settings in applications involving power transformers.
837723A1.CDR
X
R
R
EAC
H
RCA
= 80
o
COMP LIMIT
= 90
o
DIR RCA
= 80
o
DIR COMP LIMIT = 90
o
RGT BLD RCA
= 80
o
LFT BLD RCA
= 80
o
X
R
X
R
X
R
R
EAC
H
RCA
= 80
o
COMP LIMIT
= 90
o
DIR RCA
= 80
o
DIR COMP LIMIT = 60
o
RGT BLD RCA
= 80
o
LFT BLD RCA
= 80
o
R
EAC
H
RCA
= 90
o
COMP LIMIT
= 90
o
DIR RCA
= 45
o
DIR COMP LIMIT = 90
o
RGT BLD RCA
= 90
o
LFT BLD RCA
= 90
o
R
EAC
H
RCA
= 80
o
COMP LIMIT
= 80
o
DIR RCA
= 45
o
DIR COMP LIMIT = 60
o
RGT BLD RCA
= 80
o
LFT BLD RCA
= 80
o
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...