GE Multilin
D60 Line Distance Protection System
5-161
5 SETTINGS
5.5 FLEXLOGIC
5
•
TIMER 1 DROPOUT DELAY:
Sets the time delay to dropout. If a dropout delay is not required, set this function to "0".
5.5.7 FLEXELEMENTS
PATH: SETTING
FLEXLOGIC
FLEXELEMENTS
FLEXELEMENT 1(8)
A FlexElement is a universal comparator that can be used to monitor any analog actual value calculated by the relay or a
net difference of any two analog actual values of the same type. The effective operating signal could be treated as a signed
number or its absolute value could be used as per user's choice.
The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period
of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as
per user's choice.
FLEXELEMENT 1
FLEXELEMENT 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
FLEXELEMENT 1 NAME:
FxE1
Range: up to 6 alphanumeric characters
MESSAGE
FLEXELEMENT 1 +IN:
Off
Range: Off, any analog actual value parameter
MESSAGE
FLEXELEMENT 1 -IN:
Off
Range: Off, any analog actual value parameter
MESSAGE
FLEXELEMENT 1 INPUT
MODE: Signed
Range: Signed, Absolute
MESSAGE
FLEXELEMENT 1 COMP
MODE: Level
Range: Level, Delta
MESSAGE
FLEXELEMENT 1
DIRECTION: Over
Range: Over, Under
MESSAGE
FLEXELEMENT 1
PICKUP: 1.000 pu
Range: –90.000 to 90.000 pu in steps of 0.001
MESSAGE
FLEXELEMENT 1
HYSTERESIS: 3.0%
Range: 0.1 to 50.0% in steps of 0.1
MESSAGE
FLEXELEMENT 1 dt
UNIT: milliseconds
Range: milliseconds, seconds, minutes
MESSAGE
FLEXELEMENT 1 dt:
20
Range: 20 to 86400 in steps of 1
MESSAGE
FLEXELEMENT 1 PKP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
FLEXELEMENT 1 RST
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
FLEXELEMENT 1 BLK:
Off
Range: FlexLogic operand
MESSAGE
FLEXELEMENT 1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
FLEXELEMENT 1
EVENTS: Disabled
Range: Disabled, Enabled
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...