5-124
D60 Line Distance Protection System
GE Multilin
5.4 SYSTEM SETUP
5 SETTINGS
5
b) BASIC CONFIGURATION
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT
BASIC CONFIGURATION
PMU1
PMU 1 BASIC
CONFIGURATION
PMU 1
FUNCTION: Disabled
Range: Enabled, Disabled
MESSAGE
PMU 1 IDCODE:
1
Range: 1 to 65534 in steps of 1
MESSAGE
PMU 1 STN:
GE-UR-PMU
Range: 32-character ASCII string truncated to 16
characters if mapped into C37.118 Default: GE-UR-PMU
MESSAGE
PMU 1 SIGNAL SOURCE:
SRC 1
Range: Available signal sources
MESSAGE
PMU 1 CLASS:
M-CLASS
Range: None, CLASS M, CLASS P
MESSAGE
PMU 1 FORMAT:
Integer
Range: Integer, Floating-point
MESSAGE
PMU 1 STYLE:
Polar
Range: Polar, Rectangular
MESSAGE
PMU 1 RATE:
10/sec
Range:1/sec, 2/sec, 4/sec, 5/sec, 10/sec, 12/sec, 15/sec,
20/sec, 25/sec, 30/sec, 50/sec, 60/sec, 100/sec, 120/sec
MESSAGE
PMU 1 PHS-1:
Off
Range: Available synchrophasor values
MESSAGE
PMU 1 PHS-1
NAME: GE-UR-PMU-PHS-1
Range: 16 -character ASCII string
MESSAGE
PMU 1 PHS-14:
Off
Range: Available synchrophasor values
MESSAGE
PMU 1 PHS-14:
NAME: GE-UR-PMU-PHS-14
Range: 16 -character ASCII string
MESSAGE
PMU 1 A-CH-1:
Off
Range: Available FlexAnalog values
MESSAGE
PMU 1 A-CH-1:
NAME: AnalogChannel1
Range: 16 -character ASCII string
MESSAGE
PMU 1 A-CH-16 (16):
Off
Range: Available FlexAnalog values
MESSAGE
PMU 1 A-CH-16 (16):
NAME: AnalogChannel16
Range: 16 -character ASCII string
MESSAGE
PMU 1 D-CH-1:
Off
Range: Available FlexLogic operands
MESSAGE
PMU 1 D-CH-1
NAME: DigChannel1
Range: 16 character ASCII string
MESSAGE
PMU 1 D-CH-1
NORMAL STATE: Off
Range: Off, On
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...