APPLICATION EXAMPLE
D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE
9–15
GROUPING I/O DATA
By default, all mapped I/O input data is grouped in one attribute and is used for polled
production data, and all mapped I/O output data is used as polled consumption (output)
data. The mailbox commands can be used to split this data into different attributes.
We have mapped 24 bytes of input data and 4 bytes of output data. The following
procedure splits the input data in 16 bytes of I/O input data and 8 bytes of explicit input
data.
1.
Click on the
Fieldbus
item and change
IO sizes
option to “User defined” as shown
below.
Figure 9-25: User defined IO sizes
2.
Set the
IO Size In
(IO input data size) to 16 bytes (i.e. 0x000A) and the
IO Size Out
(IO
output data size) to 4 bytes.
Figure 9-26: Setting the IO sizes
3.
With this setting, input data is divided into two parts: the first 16 bytes of input is IO
input data and remaining 8 bytes is explicit input data. All 4 bytes of output data is IO
output data.
I/O DATA
INPUT MAPPING
The IO data can be further assigned to different attributes of I/O data input mapping object
A0h. Define the following five attributes out of 16 bytes of data.
Attribute
Bytes
Assignment
Attribute 1 (Input 1)
6 bytes
Phase current Ia, Ib, Ic
Attribute 2 (Input 2)
2 bytes
Average phase current
Attribute 3 (Input 3)
2 bytes
Neutral current
Attribute 4 (Input 4)
4 bytes
Average phase voltage
Attribute 5 (Input 5)
2 bytes
Motor status
Содержание D485
Страница 32: ...3 14 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE DATA EXCHANGE ...
Страница 46: ...4 14 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE SOFTWARE OVERVIEW ...
Страница 52: ...5 6 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE COMMUNICATION MODEL ...
Страница 92: ...9 20 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE APPLICATION EXAMPLE ...
Страница 94: ...10 2 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE MISCELLANEOUS ...