2-26
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS
CHAPTER 2: PRODUCT DESCRIPTION
2
Operating mode:
level, delta
Comparator direction:
over, under
Pickup Level:
–90.000 to 90.000 pu in steps of 0.001
Hysteresis:
0.1 to 50.0% in steps of 0.1
Delta dt:
20 ms to 60 days
Pickup and dropout delay:
0.000 to 65.535 s in steps of 0.001
NON-VOLATILE LATCHES
Type:
set-dominant or reset-dominant
Number:
16 (individually programmed)
Output:
stored in non-volatile memory
Execution sequence:
as input prior to protection, control, and FlexLogic
USER-PROGRAMMABLE LEDs (Enhanced and standard front panels)
Number:
48 plus trip and alarm
Programmability:
from any logical variable, contact, or virtual input
Reset mode:
self-reset or latched
LED TEST
Initiation:
from any contact input or user-programmable condition
Number of tests:
3, interruptible at any time
Duration of full test:
approximately 3 minutes
Test sequence 1:
all LEDs on
Test sequence 2:
all LEDs off, one LED at a time on for 1 s
Test sequence 3:
all LEDs on, one LED at a time off for 1 s
USER-DEFINABLE DISPLAYS (Enhanced and standard front panels)
Number of displays:
16
Lines of display:
2
×
20 alphanumeric characters
Parameters:
up to 5, any Modbus register addresses
Invoking and scrolling:
keypad, or any user-programmable condition, including pushbuttons
CONTROL PUSHBUTTONS (Enhanced and standard front panels)
Number of pushbuttons:
7
Operation:
drive FlexLogic operands
USER-PROGRAMMABLE PUSHBUTTONS (Optional)
Number of pushbuttons:
12 on standard front panel
16 on enhanced horizontal front panel
6 on enhanced vertical front panel
16 on graphical front panel (8 physical pushbuttons, 8 graphical interface pushbuttons)
Mode:
self-reset, latched
Display message:
2 lines of 20 characters each
Drop-out timer:
0.00 to 60.00 s in steps of 0.05
Autoreset timer:
0.2 to 600.0 s in steps of 0.1
Hold timer:
0.0 to 10.0 s in steps of 0.1
SELECTOR SWITCH
Number of elements:
2
Upper position limit:
1 to 7 in steps of 1
Selecting mode:
time-out or acknowledge
Time-out timer:
3.0 to 60.0 s in steps of 0.1
Control inputs:
step-up and 3-bit
Power-up mode:
restore from non-volatile memory or synchronize to a 3-bit control input or synch/restore mode
DIGITAL ELEMENTS
Number of elements:
48
Operating signal:
any FlexLogic operand
Содержание D30 series
Страница 10: ...x D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 52: ...2 38 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 534: ...5 324 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 564: ...6 30 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 578: ...7 14 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 614: ...9 26 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 654: ...A 10 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 662: ...C 6 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 670: ...iv D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 686: ...xvi D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL INDEX ...