5-176
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
FLEXLOGIC
CHAPTER 5: SETTINGS
5
Some operands can be re-named. These are the names of the breakers in the breaker control feature, the ID (identification)
of contact inputs and outputs, the ID of virtual inputs, and the ID of virtual outputs. If the user changes the default name or
ID of any of these operands, the assigned name appears in the relay list of operands. The default names are shown in the
FlexLogic operands table.
The characteristics of the logic gates are tabulated in the following table, and the operators available in FlexLogic are
listed in the FlexLogic operators table.
Table 5-21: FlexLogic gate characteristics
Table 5-22: FlexLogic operators
PUSHBUTTON 2 to 6, 12, or 16
depending on front panel
Same set of operands as PUSHBUTTON 1
Gates
Number of inputs
Output is ‘1’ (= ON) if...
NOT
1
input is ‘0’
OR
2 to 16
any input is ‘1’
AND
2 to 16
all inputs are ‘1’
NOR
2 to 16
all inputs are ‘0’
NAND
2 to 16
any input is ‘0’
XOR
2
only one input is ‘1’
Type
Syntax
Description
Notes
Editor
INSERT
Insert a parameter in an equation list
DELETE
Delete a parameter from an equation list
End
END
The first END encountered signifies the last entry in
the list of processed FlexLogic parameters
One-shot
POSITIVE ONE SHOT
One shot that responds to a positive going edge
A ‘one shot’ refers to a single input gate that
generates a pulse in response to an edge on
the input. The output from a ‘one shot’ is
True (positive) for only one pass through the
FlexLogic equation. There is a maximum of
64 ‘one shots.’
NEGATIVE ONE SHOT
One shot that responds to a negative going edge
DUAL ONE SHOT
One shot that responds to both the positive and
negative going edges
Logic
gate
NOT
Logical NOT
Operates on the previous parameter
OR(2)
↓
OR(16)
2 input OR gate
↓
16 input OR gate
Operates on the 2 previous parameters
↓
Operates on the 16 previous parameters
AND(2)
↓
AND(16)
2 input AND gate
↓
16 input AND gate
Operates on the 2 previous parameters
↓
Operates on the 16 previous parameters
NOR(2)
↓
NOR(16)
2 input NOR gate
↓
16 input NOR gate
Operates on the 2 previous parameters
↓
Operates on the 16 previous parameters
NAND(2)
↓
NAND(16)
2 input NAND gate
↓
16 input NAND gate
Operates on the 2 previous parameters
↓
Operates on the 16 previous parameters
XOR(2)
2 input Exclusive OR gate
Operates on the 2 previous parameters
LATCH (S,R)
Latch (set, reset): reset-dominant
The parameter preceding LATCH(S,R) is the
reset input. The parameter preceding the
reset input is the set input.
Timer
TIMER 1
↓
TIMER 32
Timer set with FlexLogic timer 1 settings
↓
Timer set with FlexLogic timer 32 settings
The timer is started by the preceding
parameter. The output of the timer is
TIMER #.
Assign
virtual
output
= Virt Op 1
↓
= Virt Op 96
Assigns previous FlexLogic operand to virtual
output 1
↓
Assigns previous FlexLogic operand to virtual
output 96
The virtual output is set by the preceding
parameter
Operand type
Operand syntax
Operand description
Содержание D30 series
Страница 10: ...x D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 52: ...2 38 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 534: ...5 324 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 564: ...6 30 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 578: ...7 14 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 614: ...9 26 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 654: ...A 10 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 662: ...C 6 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 670: ...iv D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 686: ...xvi D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL INDEX ...