CHAPTER 5: SETTINGS
PRODUCT SETUP
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
5-35
5
Number of Integers
Range: 1 to 12 in steps of 1
Default: 1
This setting specifies the number of integers in the displayed metered value. It can be used to provide for leading
character spacing of the display value.
For example, setting the number to 2 displays 00.000[V] and setting it to 3 displays 000.000[V].
Number of Decimals
Range: 0 to 10 in steps of 1
Default: 3
This setting specifies the number of decimal places in the displayed metered value. For example, setting the number to 1
displays 0.0 and setting it to 2 displays 0.00.
5.3.3.4 Single-line diagram editor
The path is
Settings > Product Setup > Graphical Panel > Single Line Diagram Editor
. Use is explained in the Interfaces
chapter.
5.3.3.5 Annunciator editor
The annunciator editor is used to create annunciator content for the graphical front panel, including alarms and actual
values. Use is explained in the Interfaces chapter.
The path is
Settings > Product Setup > Graphical Panel > Annunciator Editor
.
To add an alarm, access the Annunciator Editor, configure the Layout and Page Name, configure the alarm or actual value,
set the text and color, then save. On the graphical front panel, view the content by pressing the
Annunciator
Tab
pushbutton at the bottom of the
Home
page. (Alarms do not display automatically.) Acknowledge or reset the alarm by
navigating to it with the arrow pushbuttons, then pressing the
ENTER
or
RESET
pushbutton.
The figure shows alarms for basic functions. The last annunciator page is named Device Alarms. Alarms are set for the
device being offline, Ethernet cable issues, unauthorized access, battery failure, and high ambient temperature. They can
reset themselves when conditions return to normal, except for unauthorized access and temperature monitoring, which
require the alarms to be acknowledged. The self-test error functions, here for Ethernet and battery failures, also have been
enabled under
Settings > Product Setup > User-Programmable Self Tests
(not shown). When the alarms are triggered,
they display with a red background. An alarm is acknowledged by using the arrow keys on the graphical front panel then
pressing the
ENTER
button.
Содержание D30 series
Страница 10: ...x D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 52: ...2 38 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 534: ...5 324 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 564: ...6 30 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 578: ...7 14 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 614: ...9 26 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 654: ...A 10 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 662: ...C 6 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 670: ...iv D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 686: ...xvi D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL INDEX ...