MA-037 - CB Watch 3 Operating Manual
v7.0 - May 2020
Page 55 of 118
Alarms can be set on the long-term gas % leak rate (the most used metric because
government and corporate targets are set in terms of % SF
6
lost to the atmosphere).
Two thresholds are required to be entered by the user during setup:
•
Warning threshold H, same for all poles
•
Alarm threshold HH, same for all poles
HMI: Settings/Gas monitoring
Figure 80
–
Gas % leak rate thresholds
The % leak rate alarms are displayed with the other gas alarms
HMI: Measurements/Alarms
Figure 81
–
Gas % leak rate alarms
Historical Graphs
On the HMI, you can view graphs displaying the history of the key gas parameters. Using the
drop-down menu, you can select either:
•
Short term graphs: with resolution of 1 value every 10 minutes
•
Long term graphs: with resolution of 1 value per day
HMI: Measurements/Gas
Figure 82
–
gas graph selection
The “short term” selection displays
the history of:
•
Gas density
•
Gas pressure at 20
o
C
•
Gas temperature