GE Multilin
C70 Capacitor Bank Protection and Control System
5-197
5 SETTINGS
5.6 GROUPED ELEMENTS
5
Figure 5–84: VOLTAGE DIFFERENTIAL SCHEME LOGIC
h) BANK PHASE OVERVOLTAGE
(ANSI 59B, IEC PTOV)
PATH: SETTINGS
GROUPED...
SETTING GROUP 1(6)
VOLTAGE...
BANK OVERVOLTAGE
BANK OVERVOLTAGE 1(3)
BANK OVERVOLTAGE 1
BANK OV 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
BANK OV 1 BUS
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
MESSAGE
BANK OV 1 NTRL
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
MESSAGE
BANK OV 1 BANK
GROUND: Grounded
Range: Grounded, Ungrounded, Ungr w/o Vn
MESSAGE
BANK OV 1 CURVE:
FlexCurve A
Range: FlexCurve A, FlexCurve B, FlexCurve C,
FlexCurve D
MESSAGE
BANK OV 1 CURVE TIME
MULTIPLIER: 1.00
Range: 1.00 to 10.00 in steps of 0.01
MESSAGE
BANK OV 1 STG 1A
PICKUP: 1.050 pu
Range: 0.800 to 2.000 pu in steps of 0.001
t
PKP
t DPO
t
PKP
t
DPO
t
PKP
t
DPO
SETTINGS
VOLTAGE DIF 1 BUS
SOURCE:
V1A
V1B
V1C
VOLTAGE DIF 1 TAP
SOURCE:
V2A
V2B
V2C
VN
SETTINGS
V
A_dif
=
|V
A_mag
-
kA
*V2A_mag
|
or
|V
A_mag
-
kA
*(V2A
-
VN)_mag
|
VOLTAGE DIF 1
MATCH FACTOR A:
SETTING
VOLTAGE DIF 1 STG
1A PICKUP:
SETTING
VOLTAGE DIF 1 STG
2A PICKUP:
SETTING
VOLTAGE DIF 1 STG
3A PICKUP:
SETTING
VOLTAGE DIF 1 STG
4A PICKUP:
VOLT DIF 1 STG 1A PKP
FLEXLOGIC OPERAND
VOLT DIF 1 STG 2A PKP
FLEXLOGIC OPERAND
VOLT DIF 1 STG 3A PKP
FLEXLOGIC OPERAND
VOLT DIF 1 STG 4A PKP
FLEXLOGIC OPERAND
t
PKP
t
DPO
TIMERS
VOLTAGE DIF 1 STG 1
PKP DELAY:
VOLTAGE DIF 1 STG 2
PKP DELAY:
VOLTAGE DIF 1 STG 3
PKP DELAY:
VOLTAGE DIF 1 STG 4
PKP DELAY:
VOLT DIF 1 STG 1A OP
VOLT DIF 1 STG 2A OP
VOLT DIF 1 STG 3A OP
FLEXLOGIC OPERAND
VOLT DIF 1 STG 4A OP
VOLT DIF 1 PKP B
VOLTAGE DIF 1 DPO
DELAY:
VOLT DIF 1 PKP A
VOLT DIF 1 PKP C
OR
VOLT DIF 1 PKP
OR
VOLT DIF 1 OP B
VOLT DIF 1 OP A
VOLT DIF 1 OP C
OR
VOLT DIF 1 OP
OR
VOLT DIF 1 DPO
PHASE C
5 cycles
0
TIMER
RUN 87V FUNCTION
PHASE B
COMMANDS
AUTO-SETTING
PROCEDURE
VOLTAGE DIF 1 BANK
GROUND:
SETTING
COMMANDS/
VOLTAGE DIF 1
AUTO-SETTING:
WRITE A NEW SETTING
AND
VC_mag > 0.25 pu
VB_mag > 0.25 pu
VA_mag > 0.25 pu
SETTINGS
VOLTAGE DIF 1
FUNCTION:
Enabled = 1
VOLT DIF 1 BLK STG1:
Off = 0
VOLT DIF 1 BLK STG2:
Off = 0
VOLT DIF 1 BLK STG3:
Off = 0
VOLT DIF 1 BLK STG4:
Off = 0
AND
INHIBIT STAGE 1
INHIBIT STAGE 3
INHIBIT STAGE 4
INHIBIT STAGE 2
AND
Manual
Auto
AND
Apply?
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
VA_dif > PICKUP
RUN
AND
VA_dif > PICKUP
RUN
AND
VA_dif > PICKUP
RUN
AND
VA_dif > PICKUP
RUN
AND
834742A1.DWG
Содержание C70
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 452: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 1 OVERVIEW 8 THEORY OF OPERATION 8 ...
Страница 474: ...9 22 C70 Capacitor Bank Protection and Control System GE Multilin 9 4 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 486: ...10 12 C70 Capacitor Bank Protection and Control System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 630: ...B 110 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Страница 688: ...F 12 C70 Capacitor Bank Protection and Control System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...